Cable tray at ladder fill
Lapad ng tray o ladder, mga tier, kg/m at ang grouping factor.
Reads AS/NZS 3000:2018, Nexans Olex The Handbook:2017, AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3008.1.1:2017 (AU). Tables checked 1 Oct 2026.
Subukan ang isang job 4
Nilalagyan ng halimbawang value ang bawat job. Palitan ang mga ito ng sarili mong value.
- Fill a plant room trayTen multicore cables on a perforated tray, with the factor for cable size.
- Lay trefoil submains on a ladderTwo single‑core circuits in trefoil, their width and kg/m.
- Find the tiers for ten feedersHow many tiers ten multicore feeders need on a narrow tray.
- Space flat mains on a ladderThree flat circuits spaced on an Australian ladder, with the grouping factor.
Mga input
Worked example gamit ang mga default na input.
- Standard
- AS/NZS 3008.1.2 (New Zealand)
- Suporta
- Perforated tray
- Lapad sa loob
- 300 mm
- Lapad na iniiwang bakante
- 25 %
- Mga cable
- Multicore (tatlong core at earth)
- Espasyo
- Magkadikit
- Mga cable sa tray
- 2 row
Kinakailangang baitang
1
- Lapad na nasasakupan ng mga cable
- 125.3mm
- Punô ng pinakapunong baitang
- 41.8%
- Cable mass sa pinakamabigat na tier
- 4.31kg/m
- Grouping factor na dadalhin sa laki ng cable
- 0.73
Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.
Mga hakbang ng kalkulasyon
- 4 × 16 mm² multicore, tig-19.7 mm78.8mm
- 3 × 6 mm² multicore, tig-15.5 mm46.5mm
- Lapad na nasasakupan ng mga cable125.3mm
- Magagamit na lapad pagkatapos ng 25 % reserve225mm
- Kinakailangang baitangResulta1
AS/NZS 3008.1.2:2017 Table 24 Note 5
- Hanay 1: 7 cable, 125.3 mm4.31kg/m
Olex Handbook
- Punô ng pinakapunong baitang41.8%
- Grouping factor na dadalhin sa laki ng cable×0.73
AS/NZS 3008.1.2:2017 Table 24 p.82
Tungkol sa calculator na ito
How this is calculated
A cable tray or ladder holds cables side by side. AS/NZS 3008.1 rates cables on trays and ladders with grouping factors that hold for one layer of cables on each tier. So the question for a tray is how wide the cables are, laid in one layer, and how many tiers that takes. This tool lays them out and reads the factor.
You pick the cable family and list the sizes and counts. The overall diameters are the cable maker's figures that the conduit fill tool also uses. A multicore cable takes one diameter of width. A single‑core three‑phase circuit takes two diameters in trefoil and three laid flat. Touching cables sit side by side. Spaced cables have one diameter between them, as Tables 23 and 24 draw, and where sizes differ the tool uses the largest.
The standard sets no fill percentage for a tray, so the width kept free for later cables is yours to choose. The tool places each cable or circuit, in the order you list them, on the first tier with room. A run that does not fit one tier takes another, and stacked tiers are at least 300 mm apart for the factors to hold.
It then reads the grouping factor for the support, the spacing, the tiers used and the most cables or circuits on one tier. A count between two printed columns reads the next column up. Past the printed counts no factor is given. The mass per metre on each tier is the maker's catalogue figure.
| Step | Table or clause | What it decides |
|---|---|---|
| Cable diameters | Olex and Prysmian catalogue diameters | The width each cable or circuit takes |
| Spacing | AS/NZS 3008.1 Tables 23 and 24 Note 1 | One diameter between spaced cables or circuits |
| One layer per tier | AS/NZS 3008.1 Tables 23 and 24 Note 5 | The tiers the run needs |
| Tier spacing | AS/NZS 3008.1 Tables 23 and 24 Note 6 | The gap between stacked tiers |
| Grouping factor | AS/NZS 3008.1 Table 23 or Table 24 | The factor to carry to the cable size |
| Mass | Olex Handbook mass per metre | The kg/m on each tier |
Worked examples
- A plant room tray: four 16 mm² and three 6 mm² multicore cables fit on 1 tier of a 300 mm perforated tray. They take 125.3 mm, a grouping factor of 0.73.
- Two 95 mm² trefoil submains on a 450 mm ladder fit on 1 tier, 60.8 mm wide, with a grouping factor of 0.95.
- Ten 35 mm² multicore feeders on a 300 mm tray need 2 tiers with a quarter of the width kept free. The fullest tier carries nine cables, a grouping factor of 0.68.
- Three flat 240 mm² circuits spaced on a 600 mm Australian ladder fit on 1 tier at a grouping factor of 1.
Limits
The tool lays one cable family at a time: multicore three core and earth cables, or single‑core three‑phase circuits. It does not mix the two, model cables in more than one layer, or check segregation between services on the same tray. Use the segregation tool for that.
Single‑core widths use the diameter of unsheathed V‑90 single cores, the conduit fill figures. A sheathed or XLPE single core is wider, so allow for it. The mass is the cable alone. Check the tray or ladder against its maker's load and span tables, with the fixings and any future cables.
See also: Cable size, Correction factors and Conduit fill.
Mga tanong
Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.
May maximum fill ba para sa cable tray?
Walang fill percentage na itinakda ang AS/NZS 3008.1 para sa tray o ladder. Ang grouping factors nito ay ipinapalagay na isang layer ng cable sa bawat tier. Isang layer ang inilalatag ng tool at pinananatili ang reserve na pipiliin mo para sa mga susunod na cable.
Ano ang ibig sabihin ng spaced sa tray?
Ang cable na may espasyo ay may isang diameter ng cable ang pagitan, gaya ng ipinapakita ng AS/NZS 3008.1 Tables 23 at 24. Kapag magkakaiba ang laki, ginagamit ng tool ang pinakamalaking diameter. Pinapataas ng espasyo ang grouping factor at mas maraming lapad ang kinukuha.
Gaano kalawak ang trefoil circuit?
Ang tatlong single‑core cable na nasa trefoil ay umuukupa ng dalawang diameter ang lapad sa tray. Kapag nakahiga nang patag, tatlong diameter ang kukunin nila. Ginagamit ng tool ang overall diameter mula sa catalogue ng cable maker.
Anong grouping factor ang ginagamit ko para sa cable size?
Binabasa ng tool ang AS/NZS 3008.1 Table 23 para sa single‑core circuit o Table 24 para sa multicore cable, sa mga tier na ginamit nito at sa pinakamaraming cable sa isang tier. Dalhin ang factor na iyon sa cable size tool.
Tinitingnan ba nito kung kayang dalhin ng tray ang bigat?
Hindi. Ibinibigay nito ang kg/m ng cable sa bawat tier mula sa catalogue ng maker. Tingnan iyon laban sa load at span table ng tray maker.
Mga worked example
Background
Mga clause at table na binabasa ng tool na ito
- AS/NZS 5000.1 cables, manufacturer dataCable overall diameters
- AS/NZS 3008.1.2:2017 Table 23Grouping factors for single‑core circuits on trays, ladder supports, racks and cleats in air
- AS/NZS 3008.1.2:2017 Table 24Grouping factors for multicore cables on trays, ladder supports, racks and cleats in air
- AS/NZS 3008.1.1:2017 Table 23Grouping factors for single‑core circuits on trays, ladder supports, racks and cleats in air
- AS/NZS 3008.1.1:2017 Table 24Grouping factors for multicore cables on trays, ladder supports, racks and cleats in air
- cable-massApproximate cable mass per metre
Bawat clause at table, kasama kung paano ito na-verify
Huling na-check ang mga table noong 1 Oct 2026.
Mga kaugnay na tool
- Cable size calculatorFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Correction factor calculatorRead each correction factor and the rating a cable needs.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Conduit fill calculatorCheck that a cable bundle fits in a conduit.AS/NZS 3008.1.2AS/NZS 3000