Total voltage drop calculator
Idagdag ang drop ng mains, submain at final laban sa 5 %.
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 1 Oct 2026.
Subukan ang isang job 4
Nilalagyan ng halimbawang value ang bawat job. Palitan ang mga ito ng sarili mong value.
- Check the total voltage drop to a shedThe mains, the shed submain and a final subcircuit added against 5 %.
- Find the drop left for a new circuitWhat 25 m of mains and a 40 m submain leave for a final subcircuit.
- Add a three phase submain to a finalThree phase mains and submain with a single phase final, added by percent.
- Use the 7 % substation limitA factory fed from its own transformer, checked against 7 %.
Mga input
Worked example gamit ang mga default na input.
- Point of supply
- Network supply (limit na 5 %)
- Standard
- NZ · AS/NZS 3008.1.2
- Power factor
- 0.9
- Mga bahagi ng run, mula sa punto ng supply
- 3 row
Kabuuang voltage drop
4.25%
- Limit ng voltage drop
- 5%
- Mains at submains
- 1.98%
- Natira para sa final subcircuit
- 3.02%
- Naiwan sa punto ng paggamit
- 0.75%
Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.
Mga hakbang ng kalkulasyon
- Bahagi 1Consumer mains
- Bahagi 1 mV/A·m2.6mV/A·m
AS/NZS 3008.1.2:2017 Cl 4.5
- Voltage drop ng bahagi 12.6V
- Voltage drop ng bahagi 1, porsyento ng 230 V1.13%
AS/NZS 3000:2018 App C Para C4.1
- Running total pagkatapos ng bahagi 11.13%
AS/NZS 3000:2018 App C Para C4.1
- Bahagi 2Submain
- Bahagi 2 mV/A·m4.09mV/A·m
AS/NZS 3008.1.2:2017 Cl 4.5
- Voltage drop ng bahagi 21.96V
- Voltage drop ng bahagi 2, porsyento ng 230 V0.85%
AS/NZS 3000:2018 App C Para C4.1
- Running total pagkatapos ng bahagi 21.98%
AS/NZS 3000:2018 App C Para C4.1
- Bahagi 3Final subcircuit
- Bahagi 3 mV/A·m16.31mV/A·m
AS/NZS 3008.1.2:2017 Cl 4.5
- Voltage drop ng bahagi 35.22V
- Voltage drop ng bahagi 3, porsyento ng 230 V2.27%
AS/NZS 3000:2018 App C Para C4.1
- Running total pagkatapos ng bahagi 34.25%
AS/NZS 3000:2018 App C Para C4.1
- Limitasyon ng voltage drop5%
AS/NZS 3000:2018 Cl 3.6.2
- Kabuuang voltage dropResulta4.25%
AS/NZS 3000:2018 Cl 3.6.2
- Mains at submains1.98%
- Natira para sa final subcircuit3.02%
AS/NZS 3000:2018 Cl 3.6.2
- Naiwan sa punto ng paggamit0.75%
Tungkol sa calculator na ito
How this is calculated
AS/NZS 3000 limits the voltage drop from the point of supply to any point in the installation. It is one limit for the whole run, not one per circuit. So the drop in the consumer mains, every submain and the final subcircuit must add up to no more than the limit. This tool adds them.
You enter each part of the run in order from the point of supply: the consumer mains, up to three submains and the final subcircuit. For each part you give the phases, the current, the route length and the cable. The tool works each part with the same calculation as the voltage drop tool. It reads the cable's resistance and reactance from AS/NZS 3008.1, finds the mV/A·m at the power factor, and gives the drop in volts.
Each drop is then taken as a percent of that part's own circuit voltage: 230 V for single phase and 400 V for three phase. Appendix C of AS/NZS 3000 adds the percents directly, so a three‑phase submain adds to a single‑phase final subcircuit with no conversion. The running total is the drop at the end of each part.
The limit is 5 % of the nominal voltage. Where the point of supply is the low voltage terminals of a substation on the premises, which supplies only this installation, it is 7 %. The clause sets no split between the parts. The tool shows what the mains and submains take, and what that leaves for a final subcircuit from the last board.
| Step | Table or clause | What it decides |
|---|---|---|
| Resistance and reactance of each part | AS/NZS 3008.1 Tables 34 and 35 | The impedance of the cable |
| Drop of each part | AS/NZS 3008.1 Cl 4.5 | The mV/A·m and the drop in volts |
| Percent of each part | AS/NZS 3000 App C Para C4.1 | The drop as a percent of its circuit voltage, added part by part |
| The limit | AS/NZS 3000 Cl 3.6.2 | The most the total may be from the point of supply |
| A substation on the premises | AS/NZS 3000 Cl 3.6.2 Exception 3 | The higher limit where it applies |
| A load spread along a final subcircuit | AS/NZS 3000 Cl 3.6.2 Exception 1 | The current you may use for that part |
Worked examples
- A house: mains, a garage submain and a socket‑outlet circuit. The total voltage drop is 4.25 %. The mains and submain take 1.98 %, which leaves 3.02 % for a final subcircuit.
- A shed 30 m from the house. The total voltage drop is 4.83 %, inside the 5 % limit but close to it. The upstream parts take 3.13 %, which leaves 1.87 % for a final subcircuit.
- A factory on its own substation. The total voltage drop is 6.27 % against the 7 % limit. The mains and submain take 4.38 %, which leaves 2.62 % for a final subcircuit.
- A farm workshop 60 m from the house. The total voltage drop is 10.82 %, so the run fails. The mains and submain take 8.55 % on their own, which leaves −3.55 % for a final subcircuit. A larger submain is the fix.
Limits
The tool works a.c. runs at 230 V and 400 V nominal. It does not check extra-low voltage circuits, which Cl 3.6.2 leaves out, or a stand-alone system, which Exception 4 judges on the utilisation voltage. Single‑core parts use the highest reactance the table gives for the formation. Use the voltage drop tool for one run with a known formation or an unbalanced neutral.
Motor starting and other short transient drops are not part of the limit. Check those against the equipment.
See also: Voltage drop, The 5 % voltage drop limit from supply to load and Total voltage drop: mains, submain and final.
Mga tanong
Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.
Para ba sa bawat circuit o sa buong installation ang 5 % voltage drop?
Ang buong installation. Nililimitahan ng AS/NZS 3000 Cl 3.6.2 ang voltage drop mula sa point of supply hanggang sa anumang point. Ang consumer mains, submains at ang final subcircuit ay nagbabahagi ng iisang 5 %, kaya ito ang idinadagdag ng tool.
May hati bang 2 % at 3 % sa pagitan ng mains at final subcircuits?
Hindi ito nasa AS/NZS 3000. Ang Cl 3.6.2 ay nagtatakda ng isang limitasyon at walang hati. Madalas magplano ng isa ang mga designer, pero ang clause ay humihingi lamang na manatili ang kabuuan sa loob ng limitasyon. Ipinapakita ng tool kung ano ang kinukuha ng mains at submains, at kung ano ang natitira.
Paano ako magdaragdag ng three‑phase submain sa single‑phase final subcircuit?
Ayon sa percent. Ang bawat bahagi ay kinukuwenta bilang percent ng sarili nitong circuit voltage, 400 V para sa three phase at 230 V para sa single phase. Diretsong idinadagdag ng Appendix C ng AS/NZS 3000 ang mga percent na iyon.
Kailan 7 % ang limit?
Kapag ang point of supply ay ang low voltage terminals ng substation sa parehong premises na nagsusupply lang sa installation na ito. Piliin ang Own substation at 7 % ang gamit ng tool.
Anong current ang dapat kong gamitin para sa bawat part?
Ang maximum demand ng bawat bahagi, ang connected load nito, o ang protective device rating nito, alinman ang alam mo. Ang final subcircuit na may load na nakakalat sa buong haba nito ay puwedeng gumamit ng kalahati ng device rating.
Mga worked example
Background
Mga clause at table na binabasa ng tool na ito
- AS/NZS 3000:2018 App C Para C4.1Adding voltage drop by percent
- AS/NZS 3000:2018 Cl 3.6.2Voltage drop limit
- AS/NZS 3000:2018 Cl 3.6.2Voltage drop limit from the point of supply, and how the parts of an installation add
- AS/NZS 3008.1.2:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2025 Table 4.1(A), 4.1(B), 4.5(A), 4.5(B)Reactance at 50 Hz and a.c. resistance at 50 Hz
Bawat clause at table, kasama kung paano ito na-verify
Huling na-check ang mga table noong 1 Oct 2026.
Mga kaugnay na tool
- Cable size calculatorFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Voltage drop calculatorCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Maximum circuit length calculatorLongest run that voltage drop and the fault loop allow.AS/NZS 3000AS/NZS 3008.1.2