Arc flash calculator

I-estimate ang enerhiya ng arc flash at ang PPE category nito.

IEEE 1584-2018IEEE 1584-2002Data na nire-review pa

Reads IEEE 1584-2002 and 2018. Tables checked 1 Oct 2026.

Mga input

Worked example gamit ang mga default na input.

Model
IEEE 1584-2018
System voltage
0.4 kV
Bolted fault current
20 kA
Clearing time
0.2 s
Oras ng clearing sa nabawasang current
0 s
Kagamitan
Switchgear
Configuration ng electrode
VCB: vertical conductors sa loob ng box
Electrode gap
0 mm
Taas ng enclosure
0 mm
Lapad ng enclosure
0 mm
Lalim ng enclosure
0 mm
Working distance
455 mm

Incident energy

7.01cal/cm²

Arcing current
13.64kA
Nabawasang arcing current
11.9kA
Arc flash boundary
1,373.09mm
PPE category
2

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. ModeloIEEE 1584-2018

    IEEE 1584-2018 Cl 4

  2. Arcing current sa 600 V16.27kA

    IEEE 1584-2018 Cl 4

  3. Configuration ng electrodeVCB

    IEEE 1584-2018 Cl 4

  4. Agwat ng electrode32mm

    IEEE 1584-2018 Cl 4

  5. Arcing current13.64kA

    IEEE 1584-2018 Cl 4

  6. Katumbas na laki ng enclosure20

    IEEE 1584-2018 Cl 4

  7. Correction factor ng laki ng enclosure×1.00

    IEEE 1584-2018 Cl 4

  8. Incident energy sa buong arcing current7.01cal/cm²

    IEEE 1584-2018 Cl 4

  9. Variation factor ng arcing current0.26

    IEEE 1584-2018 Cl 4

  10. Binawasang arcing current11.9kA

    IEEE 1584-2018 Cl 4

  11. Incident energy sa nabawasang arcing current6.15cal/cm²

    IEEE 1584-2018 Cl 4

  12. Incident energy, ang mas mataas na passResulta7.01cal/cm²

    IEEE 1584-2018 Cl 4

  13. Arc flash boundary, ang mas mataas na pass1,373.09mm

    IEEE 1584-2018 Cl 4

Tungkol sa calculator na ito

How this is calculated

The tool estimates the incident energy of an arcing fault. It uses the IEEE 1584-2018 model. It can also run the 2002 model for older studies. IEEE 1584 is not an AS/NZS Standard, so the steps cite its clause only.

  1. Model. You pick the 2018 or the 2002 model. The 2018 model asks for the electrode configuration and the equipment. The 2002 model asks if the equipment is enclosed and earthed (Cl 4).
  2. Arcing current. The tool finds the arcing current at 600 V. It then corrects it to your voltage for the electrode gap.
  3. Enclosure. It works the equivalent enclosure size. It applies the enclosure size correction factor.
  4. Incident energy. It works the incident energy at the full arcing current. It uses your clearing time and working distance.
  5. Reduced current. It applies an arcing current variation factor. It works the incident energy again at that lower current.
  6. Result. The tool keeps the higher of the two passes. It gives the arc flash boundary and the PPE category.
StepTable or clauseWhat it decides
Arcing currentIEEE 1584-2018 Cl 4The current at your voltage and gap
Enclosure correctionIEEE 1584-2018 Cl 4The effect of the box size
Incident energy and boundaryIEEE 1584-2018 Cl 4The energy and the distance for the higher pass

Worked example

Limits

  • The 2018 model covers 208 V to 15 kV. Above 15 kV the tool uses the Lee model, which is a different method.
  • The reduced current pass uses the same clearing time. Enter its own time from the device curve.
  • The tool takes your bolted fault current and clearing time as given. Get them from a fault level study and the device curve.
  • The result is an estimate. It is not a label and it is not a safe-work permit.

See also: Arc flash basics, Incident energy at a 400 V switchboard and Arc flash label for a commercial main switchboard.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Ano ang ginagawa ng arc flash calculator?

Tinatantiya ng tool ang arcing current, pagkatapos ang arc flash boundary. Tinatantiya rin nito ang incident energy sa working distance mo, at iniuulat ang PPE category para sa energy na iyon. Ipinapakita ng mga hakbang ang bawat value na ginamit ng model.

Aling model ang ginagamit nito?

Gumagamit ng IEEE 1584-2018 model ang bagong page. Piliin ang 2002 para tumugma sa mas lumang pag-aaral. Ang link o save na ginawa bago ang 2018 model ay bumabasa bilang 2002, kaya hindi nagbabago ang resulta nito. Kapag higit sa 15 kV, walang nalalapat na model, kaya gumagamit ang tool ng Lee method at sinasabi ito.

Aling mga input ang pinakamahalaga?

Ang bolted fault current at ang clearing time ang pangunahing nagtatakda ng incident energy. Mahalaga rin ang working distance, na default na 455 mm. Sa 2018 model, binabago ng electrode configuration at laki ng enclosure ang energy. Ang VCB, vertical conductors in a box, ang karaniwang kaso sa switchboard. Sa 2002 model, mahalaga ang mga setting na enclosed at earthed.

Bakit tumatakbo nang dalawang beses ang 2018 model?

Nag-iiba ang arcing current sa bawat test. Kaya tumatakbo rin ang tool sa nabawasang arcing current, na maaaring magdulot ng mas mabagal na trip ng device. Iniuulat nito ang mas mataas na energy at ang mas malaking boundary. Ilagay ang clearing time sa nabawasang current kung iba ang oras na ibinibigay ng device curve mo.

Paano pinipili ang PPE category?

Itinatakda ng tool ang category mula sa incident energy. Ang mga gilid ng band na ginagamit nito ay 1.2, 4, 8, 25 at 40 calories kada square centimetre. Kapag higit sa 40, iniuulat ang resulta bilang higit sa category 4. Nasa page address ang mga input, kaya muling nagagawa ng link ang study case.