Cable loss running cost

Ano ang natitipid sa energy, gastos at CO2 kapag nag-size up ng cable.

AS/NZS 3008.1

Reads AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3008.1.1:2017 (AU). Tables checked 24 Sept 2026.

Mga input

Worked example gamit ang mga default na input.

Hurisdiksyon
NZ · AS/NZS 3008.1.2
Mga phase
Three phase
Running current, rms
100 A
Oras ng takbo kada taon
4,000 h
Haba ng ruta
60 m
Conductor
Tanso
Insulation
XLPE 90 °C
Sukat na pumapasa
35 mm²
Sukat na ikukumpara
50 mm²
Energy tariff
0.3 $/kWh
Emission factor
0.1 kg/kWh
Dagdag na gastos ng mas malaking laki
800 $

Natipid na gastos kada taon

$375.84

Natipid na enerhiya kada taon
1,252.8kWh
CO2 na natipid kada taon
125.3kg
Pagbabalik ng dagdag na gastos
2.1years
Enerhiyang nawawala kada taon, 35 mm²
4,809.6kWh
Enerhiyang nawawala kada taon, 50 mm²
3,556.8kWh

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. 35 mm² a.c. resistance sa 90 °C0.67Ω/km

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  2. 35 mm² loss: 3 × 100² × R × 60 m1,202.4W
  3. 35 mm² na enerhiyang nawawala kada taon, sa loob ng 4000 h4,809.6kWh
  4. 35 mm² ang gastos kada taon, sa $0.30 bawat kWh$1,442.88
  5. 50 mm² a.c. resistance sa 90 °C0.49Ω/km

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  6. 50 mm² loss: 3 × 100² × R × 60 m889.2W
  7. 50 mm² na enerhiyang nawawala kada taon, sa loob ng 4000 h3,556.8kWh
  8. 50 mm² ang gastos kada taon, sa $0.30 bawat kWh$1,067.04
  9. Natipid na enerhiya kada taon1,252.8kWh
  10. Natipid na gastos kada taonResulta$375.84
  11. CO2 na natipid kada taon125.3 kg
  12. Pagbabalik ng dagdag na gastos2.1 taon

Tungkol sa calculator na ito

How this is calculated

Every cable turns some of the energy it carries into heat. The loss is the current squared times the resistance of the conductors that carry it. A larger cable has less resistance, so it wastes less. This tool puts a yearly figure on that waste for two sizes, so you can see what the size up saves.

The tool reads the a.c. resistance of each size from AS/NZS 3008.1, in ohms per kilometre, for the conductor metal and insulation you pick. It reads the table at the conductor's full-load temperature. On a single‑phase circuit the current flows out and back, so two conductors carry the loss. On a balanced three‑phase circuit the neutral carries no current, so three do.

The loss in watts is the number of loaded conductors times the current squared times the resistance times the length. The tool multiplies it by the running hours a year to get kWh. The tariff turns kWh into dollars, and the emission factor turns kWh into kilograms of CO2. Both are figures you set from your own contract and grid.

The difference between the two sizes is the saving a year. If you enter what the size up costs over the smaller cable, installed, the tool divides that by the saving to give the payback in years.

Enter the rms current over the running hours, not the mean or the peak. Loss grows with the square of the current, so a cable that runs near full load for long hours gains the most from a size up.

StepTable or clauseWhat it decides
Resistance of each sizeTables 34 and 35The ohms per kilometre at the full-load temperature
Lossn × I² × R × LThe watts each size wastes
Energy a yearLoss × running hoursThe kWh each size wastes
Cost and CO2Tariff and emission factorDollars and kilograms a year, from your figures
PaybackExtra cost ÷ saving a yearThe years for the size up to pay for itself

Worked examples

Limits

The resistance is the table figure at the full-load temperature. A cable at part load runs cooler, so the real loss is a little lower than the tool shows.

The tool does not size the cable. Size it first for current, voltage drop and fault with the cable size tool, then compare the size that passes with the next size up. It does not count the time value of money, a tariff that changes through the day, or harmonic currents, which add loss.

See also: Cable size, Voltage drop and Three phase power.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Paano kinakalkula ang enerhiyang nawawala sa cable?

I-multiply ang bilang ng loaded conductor sa current squared, sa resistance kada metro, at sa haba. Iyon ang loss sa watts. I-multiply ang loss sa running hours, hinati sa 1000, para makuha ang kWh kada taon. Binabasa ng tool ang resistance mula sa AS/NZS 3008.1.

Nakakatipid ba ang mas malaking cable?

Mas mababa ang resistance ng mas malaking cable, kaya mas kaunti ang nawawalang enerhiya. Sa mahabang run na may mataas na current sa maraming oras, puwedeng mabawi ng tipid ang dagdag na cable sa loob ng ilang taon. Sa maikli o bihirang gamiting run, bihira itong mangyari.

Bakit upper bound ang loss?

Binabasa ng tool ang resistance sa full-load temperature ng cable, 75 °C para sa PVC at 90 °C para sa XLPE. Ang cable sa part load ay mas malamig ang takbo at mas mababa ang resistance nito, kaya bahagyang mas mababa ang tunay na loss. Ganoon din ang savings, at ang payback ay lower bound.

Anong tariff at emission factor ang dapat kong gamitin?

Gamitin ang energy rate sa kontrata ng supply mo, kasama ang anumang time-of-use split na tumutugma sa mga oras. Para sa CO2, gamitin ang inilathalang emission factor ng grid mo. Pareho itong assumption na ikaw ang nagtatakda. Walang hawak ang AmpSize sa alinman sa dalawa.

Pinapalitan ba nito ang cable size check?

Hindi. I-size muna ang cable para sa current, voltage drop at fault gamit ang cable size tool. Pagkatapos, ihambing ang size na pumasa sa susunod na mas malaking size dito.

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 24 Sept 2026.