Voltage Rise calculator

Voltage rise calculator para sa solar at embedded generation sa New Zealand at Australia, sinuri laban sa limit ng AS/NZS 4777.1.

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 4777.1:2016. Tables checked 27 Sept 2026.

Mga input

Worked example gamit ang mga default na input.

Mga phase
Single phase
Voltage
230 V
Output ng inverter
5 kW
Power factor
1
Haba ng run
30 m
Standard
NZ · AS/NZS 3008.1.2
Cable
10 mm² Tanso PVC 75 °C
Limitasyon ng voltage rise
2 %

Voltage rise

1.26%

Current ng inverter
21.74A
Voltage rise
2.91V
Pinakamahabang haba sa limit
47.44m
Limitasyon ng voltage rise
2%

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Output current ng inverter21.74A
  2. Resistance2.23Ω/km

    AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103

  3. mV/A·m4.46mV/A·m

    AS/NZS 3008.1.2:2017 Cl 4.5

  4. Voltage rise2.91V
  5. Voltage rise, porsyentoResulta1.26%
  6. Pinakamahabang haba47.44m

Tungkol sa calculator na ito

How this is calculated

The tool works out the voltage rise on the cable between an inverter and its point of supply. It uses the cable data of AS/NZS 3008.1.2:2017. The Australian choice reads AS/NZS 3008.1.1:2025 and the superseded 2017 edition.

  1. Inverter current. The tool divides the inverter power by the voltage and the power factor. On three phases, it also divides by the square root of three.
  2. Resistance and reactance. It reads the conductor resistance from Tables 34 and 35. It reads the reactance from Table 30. It uses the value for your size, material and insulation.
  3. Millivolts per ampere metre. It combines both values with the power factor. This is the method of Cl 4.5.
  4. Voltage rise. It multiplies the millivolts per ampere metre by the current and the run length. It gives the result in volts and as a percentage of the supply voltage.
  5. Maximum length. It finds the run length at which the rise equals your limit.

The limit is an input. AS/NZS 3000:2018 Cl 3.6.2 Note 3 refers the rise limit to AS/NZS 4777.1. Check the current edition for the value that applies to your site.

Worked example

  • 5 kW inverter on 30 m of 10 mm² copper. The supply is single‑phase at 230 V with a power factor of 1. The inverter current is 21.74 A. The voltage rise is 2.91 V, or 1.26 %. That is within a limit of 2 %. The longest run at that limit is 47.44 m.

Limits

The limit of 2 % is a default you can change. It is not a value read from a standard. The tool does not check the inverter voltage settings or the rules of the network operator.

The reactance is the Table 30 value for a multicore cable. A single‑core run reads a higher reactance for its formation. The tool does not size the cable for current. Use the cable size calculator for that.

See also: Solar inverter voltage rise at 5 kW, Voltage rise on a long rural PV run and the PV string tool.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Ano ang ginagawa ng voltage rise calculator?

Kinakalkula ng tool ang inverter output current mula sa rating nito, sa voltage at sa power factor. Pagkatapos, kinakalkula nito ang voltage rise sa kahabaan ng cable papunta sa point of supply mo, sa volts at bilang porsyento. Iniuulat din nito ang pinakamahabang run na nakakatugon pa rin sa limit.

Anong voltage rise limit ang ginagamit ng tool?

Ginagamit ng tool ang 2 porsyento bilang sariling default, at puwede mo itong baguhin. Tinutukoy ng AS/NZS 3000:2018 Clause 3.6.2 Note 3 ang voltage rise sa AS/NZS 4777.1. Walang hawak na AS/NZS 4777.1 ang AmpSize. Basahin ang kasalukuyang edition ng AS/NZS 4777.1 para sa limit na nalalapat sa site mo.

Aling mga input ang pinakamahalaga?

Direktang nag-i-scale ang rise sa inverter rating at sa run length. Itinatakda ng laki at material ng conductor ang resistance. Limitado sa range na 0.8 hanggang 1 ang power factor, at default ito na 1, na karaniwang kaso para sa inverter. Hinahati ng mga cable na parallel ang impedance.

Ano pa ang dapat kong suriin?

Sakop lang ng tool na ito ang voltage rise sa inverter cable. Hindi nito sakop ang supply network, protection o anti islanding. Gamitin ang cable size tool para suriin ang current rating ng parehong cable. Nasa page address ang mga input, kaya muling nagagawa ng link ang kalkulasyon.

Mga worked example

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 27 Sept 2026.

Nakatulong ba ito?

May tanong, o may value na mukhang mali? Makipag-ugnayan sa amin.