Power factor correction calculator

Hanapin ang capacitor kvar para itaas ang power factor.

Reads AS/NZS 3000:2018.

Mga input

Worked example gamit ang mga default na input.

Itama
Isang load o isang board
Mga phase
Three phase
Voltage
400 V
Yunit ng load
kW
Load
100
Kasalukuyang power factor
0.75
Target power factor
0.95
Bank step
25 kvar
Current harmonic distortion (THDi)
0 %
Fault level sa bank
0 MVA

Kailangan ng correction

55.32kvar

Naka-install na bank
3 × 25kvar
Power factor kasama ang bank
0.991
Current bago
192.45A
Current pagkatapos
145.59A
Nailabas na kapasidad
32.47kVA
Mga konduktor ng bank, hindi bababa sa
146.14A

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Real power100kW
  2. Reactive power sa kasalukuyang power factor88.19kvar
  3. Reactive power sa target na power factor32.87kvar
  4. Kailangan ng correctionResulta55.32kvar
  5. Mga bank step

    3 × 25 kvar

  6. Power factor kasama ang bank0.99
  7. Current bago192.45A
  8. Current pagkatapos145.59A
  9. Nailabas na kapasidad32.47kVA
  10. Rated current ng bank108.25A
  11. Pinakamababang capacity ng bank conductor, 135 %146.14A

    AS/NZS 3000:2018 Cl 4.15.2.3

Tungkol sa calculator na ito

How this is calculated

The tool finds the capacitor bank that lifts a load to a target power factor. It then gives the current before and after.

  1. Real power. You enter kW, or kVA with a power factor. The tool finds the real power.
  2. Reactive power. It finds the reactive power at the present power factor. It does the same at the target.
  3. Correction required. The difference is the kvar the bank must supply.
  4. Bank steps. It rounds up to whole steps of the size you enter. It then recalculates the power factor with that bank.
  5. Currents. It finds the current before and after. The difference is the capacity the bank releases.
  6. Bank conductors. It sizes the bank conductors at 135 % of the bank rated current. This follows AS/NZS 3000 Cl 4.15.2.3.

AS/NZS 3000 Cl 4.15.2.2 covers switching, and Cl 4.15.3.1 covers discharge.

Worked example

One motor

Set Correct to one motor to size a capacitor fitted at a motor and switched with it. The capacitor must not supply more than the motor's own magnetising kvar. If it does, the motor, still turning after it is switched off, can excite itself from the capacitor and raise its voltage. The tool takes the no-load current as all magnetising and keeps the capacitor to 90 % of the no-load kvar, a rule of practice. It fits the smaller of that and the kvar to reach the target at full load, then gives the line current with it from the motor tool's full load current.

Limits

The tool does not assess harmonics unless you enter the THDi. Switch each step with a device rated for capacitors. The tool does not model resonance with the supply.

See also: Power factor and reactive power, Power factor correction for a 250 kW factory and Three phase power.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Gaano kalaking capacitor ang puwede kong ilagay sa motor?

Hindi hihigit sa mga 90 % ng no-load kvar ng motor, bilang rule of thumb. Kapag mas malaki, puwedeng mag-self-excite ang motor pagkatapos itong i-switch off. Itakda ang tool sa One motor at ilagay ang no-load current.

Paano kinakalkula ang kvar?

Hinahanap ng tool ang reactive power sa kasalukuyang power factor at sa target, parehong mula sa real power. Ang pagkakaiba ay ang kvar na dapat ibigay ng bank. Pagkatapos, nire-round up ito sa buong bank step.

Bakit bumababa ang current pagkatapos ng correction?

Nananatiling pareho ang real power, pero ang bank ang nagbibigay ng reactive power sa site. Kaya mas kaunting apparent power ang dinadala ng supply. Bumababa ang current nang proporsyonal, at ang kVA na napalaya nito ay ang released capacity.

Kailan ko kailangan ang detuned bank?

Ang drives, rectifiers at LED drivers ay humihila ng harmonic currents. Ang plain capacitors ay puwedeng mag-resonate sa supply at palakasin ang mga ito. Bilang panuntunan, kapag higit sa humigit-kumulang 10 % THDi, maglagay ng detuned bank na may series reactors. Kapag higit sa 20 %, kumuha ng harmonic study.

Ano ang ibig sabihin ng resonance order?

Ang capacitor bank at ang supply ay bumubuo ng tuned circuit. Ang order ay ang square root ng fault level na hinati sa bank kvar. Kapag malapit sa ika-5, ika-7, ika-11 o ika-13 na harmonic, binabalaan ka ng tool.

Mga worked example

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Nakatulong ba ito?