AS/NZS 3012:2019

Cl 2.4.6 and Table 6

RCD protection and periodic verification intervals for a site under construction or demolition

The construction site supply tool reads the RCD requirement for the circuit and the periodic verification intervals of Table 6, including the note that the transportable structure intervals do not apply in New Zealand.

已核验:对照印刷版标准阅读,页码 15–17, 19–20, 25, 35–37, 44。检查于 1 Oct 2026。

单位:Required ma mA, Interval months months

这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。

返回 AS/NZS 3012:2019 页面上的对应卡片

10 行

Cl 2.4.6 and Table 6, RCD protection and periodic verification intervals for a site under construction or demolition
CaseClauseRequired ma (mA)All live conductorsLocationsExceptionsNz only exceptionsEquipmentInterval monthsNz transportable structures exempt
construction-final2.4.6.130yesoriginating-switchboardmechanical-operation-at-risk, selv-or-pelv, safety-isolating-transformer, nz-110v-centre-tapped-transformernz-110v-centre-tapped-transformer
permanent-final2.4.6.230nooriginating-switchboard, socket‑outlet, portable-socket‑outlet-assembly—
generator-supplied2.4.6.330yesoriginating-switchboard, generatorisolated-winding-generator
inverter-supplied2.4.6.430noinverterisolated-inverter
3.3, 3.5construction-wiring6yes
3.5portable-equipment3no
3.4portable-rcd-pushbutton—no
3.4fixed-rcd-pushbutton1no
3.4portable-rcd-operating-time3no
3.4fixed-rcd-operating-time12no