AS/NZS 3012:2019
Cl 2.4.6 and Table 6
RCD protection and periodic verification intervals for a site under construction or demolition
The construction site supply tool reads the RCD requirement for the circuit and the periodic verification intervals of Table 6, including the note that the transportable structure intervals do not apply in New Zealand.
Na-verify: binasa laban sa naka-print na standard, mga pahina 15–17, 19–20, 25, 35–37, 44. Na-check noong 1 Oct 2026.
Mga unit: Required ma mA, Interval months months
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
10 na row
| Case | Clause | Required ma (mA) | All live conductors | Locations | Exceptions | Nz only exceptions | Equipment | Interval months | Nz transportable structures exempt |
|---|---|---|---|---|---|---|---|---|---|
| construction-final | 2.4.6.1 | 30 | yes | originating-switchboard | mechanical-operation-at-risk, selv-or-pelv, safety-isolating-transformer, nz-110v-centre-tapped-transformer | nz-110v-centre-tapped-transformer | |||
| permanent-final | 2.4.6.2 | 30 | no | originating-switchboard, socket‑outlet, portable-socket‑outlet-assembly | — | ||||
| generator-supplied | 2.4.6.3 | 30 | yes | originating-switchboard, generator | isolated-winding-generator | ||||
| inverter-supplied | 2.4.6.4 | 30 | no | inverter | isolated-inverter | ||||
| 3.3, 3.5 | construction-wiring | 6 | yes | ||||||
| 3.5 | portable-equipment | 3 | no | ||||||
| 3.4 | portable-rcd-pushbutton | — | no | ||||||
| 3.4 | fixed-rcd-pushbutton | 1 | no | ||||||
| 3.4 | portable-rcd-operating-time | 3 | no | ||||||
| 3.4 | fixed-rcd-operating-time | 12 | no |