AS/NZS 3012:2019

Cl 2.4.6 and Table 6

RCD protection and periodic verification intervals for a site under construction or demolition

The construction site supply tool reads the RCD requirement for the circuit and the periodic verification intervals of Table 6, including the note that the transportable structure intervals do not apply in New Zealand.

Na-verify: binasa laban sa naka-print na standard, mga pahina 15–17, 19–20, 25, 35–37, 44. Na-check noong 1 Oct 2026.

Mga unit: Required ma mA, Interval months months

Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.

Bumalik sa card nito sa page ng AS/NZS 3012:2019

10 na row

Cl 2.4.6 and Table 6, RCD protection and periodic verification intervals for a site under construction or demolition
CaseClauseRequired ma (mA)All live conductorsLocationsExceptionsNz only exceptionsEquipmentInterval monthsNz transportable structures exempt
construction-final2.4.6.130yesoriginating-switchboardmechanical-operation-at-risk, selv-or-pelv, safety-isolating-transformer, nz-110v-centre-tapped-transformernz-110v-centre-tapped-transformer
permanent-final2.4.6.230nooriginating-switchboard, socket‑outlet, portable-socket‑outlet-assembly—
generator-supplied2.4.6.330yesoriginating-switchboard, generatorisolated-winding-generator
inverter-supplied2.4.6.430noinverterisolated-inverter
3.3, 3.5construction-wiring6yes
3.5portable-equipment3no
3.4portable-rcd-pushbutton—no
3.4fixed-rcd-pushbutton1no
3.4portable-rcd-operating-time3no
3.4fixed-rcd-operating-time12no