AS/NZS 3000:2018
Table C8
Simplified voltage drop, ampere metres per percent
The simplified selector reads the ampere metres per percent of voltage drop that Table C8 gives. It reads them for each conductor size, for one phase and for three. The table stops at 95 mm², and the tool says so rather than extrapolating.
Kua manatokotia: pānuitia ki te paerewa tā, whārangi 481. I tirohia 26 Sept 2026.
Ngā unit: Size mm2, Am per percent A*m per %
Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.
12 rārangi
| Size (mm2) | Single phase | Three phase |
|---|---|---|
| 1 | 45 | 90 |
| 1.5 | 70 | 140 |
| 2.5 | 128 | 256 |
| 4 | 205 | 412 |
| 6 | 306 | 615 |
| 10 | 515 | 1034 |
| 16 | 818 | 1643 |
| 25 | 1289 | 2588 |
| 35 | 1773 | 3560 |
| 50 | 2377 | 4772 |
| 70 | 3342 | 6712 |
| 95 | 4445 | 8927 |