AS/NZS 3000:2018

Table C6, C7

Simplified protective device selection for 1 to 25 mm² cables

The simplified selector reads the largest protective device rating Tables C6 and C7 allow for a conductor size. It reads one for each installation condition the tables separate, for circuits of one phase and of three.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 478–479. I tirohia 26 Sept 2026.

Ngā unit: Size mm2, Rating A

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3000:2018

16 rārangi

Table C6, C7, Simplified protective device selection for 1 to 25 mm² cables
PhasesSize (mm2)In air unenclosedThermal insulation partialThermal insulation completeIn air enclosedIn ground enclosed
11161081316
11.52016101620
12.52520162032
143225202540
164032253250
1106350325063
1168063406380
125100805080100
31131061316
31.5161381620
32.52016102025
343220162532
364032203240
3105040254050
3166350326363
3258063408080