AS/NZS 3000:2018
Table C8
Simplified voltage drop, ampere metres per percent
The simplified selector reads the ampere metres per percent of voltage drop that Table C8 gives. It reads them for each conductor size, for one phase and for three. The table stops at 95 mm², and the tool says so rather than extrapolating.
تم التحقق: مقروء مقابل المعيار المطبوع، الصفحات 481. تم التحقق في 26 Sept 2026.
الوحدات: Size mm2, Am per percent A*m per %
هذه هي القيم التي ترمّزها AmpSize. لا يُعاد إنتاج أي نص من المعيار. تحقق من المعيار الحالي.
12 صفوف
| Size (mm2) | Single phase | Three phase |
|---|---|---|
| 1 | 45 | 90 |
| 1.5 | 70 | 140 |
| 2.5 | 128 | 256 |
| 4 | 205 | 412 |
| 6 | 306 | 615 |
| 10 | 515 | 1034 |
| 16 | 818 | 1643 |
| 25 | 1289 | 2588 |
| 35 | 1773 | 3560 |
| 50 | 2377 | 4772 |
| 70 | 3342 | 6712 |
| 95 | 4445 | 8927 |