Table 3.3

Nominal minimum cross-sectional area of conductors

The minimum conductor size tool reads the smallest conductor Table 3.3 allows for the circuit use, the wiring type and the conductor material. Exception 1 can allow a smaller socket‑outlet conductor, and the tool points at it instead of applying it.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 158, 160. I tirohia 26 Sept 2026.

Ngā unit: Size mm2

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3000:2018

7 rārangi

Table 3.3, Nominal minimum cross-sectional area of conductors
UseWiringMaterialSize (mm2)
socket‑outletsinsulatedCu2.5
other-circuitsinsulatedCu1
signal-and-relay-controlinsulatedCu0.5
barebareCu6
flexibleinsulated-flexibleCu0.75
aerialaerialCu6
aerialaerialAl16