Minimum cable size for a lighting circuit

Rapu rahi kaikawe iti rawa

Worked to AS/NZS 3000:2018. Tables checked 26 Sept 2026.

Rahi kaikawe iti rawa

1mm²

Whakatuwhera te tātaitai me ēnei whakauru

He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.

A drawn result card from the Minimum Conductor Size tool: minimum conductor size 1 mm².

The minimum copper conductor for a lighting circuit is 1 mm². AS/NZS 3000:2018 Table 3.3 gives that size for every circuit other than socket‑outlets, and a lighting circuit is one of them.

A floor, not a design

The minimum size does not account for the load or the run. A lighting circuit over a long run reaches the voltage drop limit first, and the cable size calculator then selects a larger size.

A socket‑outlet on the same circuit changes the row. Table 3.3 then sets the socket‑outlet minimum instead.

See also: What size cable for a lighting circuit in NZ? and Minimum cable size for power points.