AS/NZS 3000:2018

Table 3.3

Nominal minimum cross-sectional area of conductors

The minimum conductor size tool reads the smallest conductor Table 3.3 allows for the circuit use, the wiring type and the conductor material. Exception 1 can allow a smaller socket‑outlet conductor, and the tool points at it instead of applying it.

Na-verify: binasa laban sa naka-print na standard, mga pahina 158, 160. Na-check noong 26 Sept 2026.

Mga unit: Size mm2

Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.

Bumalik sa card nito sa page ng AS/NZS 3000:2018

7 na row

Table 3.3, Nominal minimum cross-sectional area of conductors
UseWiringMaterialSize (mm2)
socket‑outletsinsulatedCu2.5
other-circuitsinsulatedCu1
signal-and-relay-controlinsulatedCu0.5
barebareCu6
flexibleinsulated-flexibleCu0.75
aerialaerialCu6
aerialaerialAl16