AS/NZS 3000:2018
Table 3.3
Nominal minimum cross-sectional area of conductors
The minimum conductor size tool reads the smallest conductor Table 3.3 allows for the circuit use, the wiring type and the conductor material. Exception 1 can allow a smaller socket‑outlet conductor, and the tool points at it instead of applying it.
已核验:对照印刷版标准阅读,页码 158, 160。检查于 26 Sept 2026。
单位:Size mm2
这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。
7 行
| Use | Wiring | Material | Size (mm2) |
|---|---|---|---|
| socket‑outlets | insulated | Cu | 2.5 |
| other-circuits | insulated | Cu | 1 |
| signal-and-relay-control | insulated | Cu | 0.5 |
| bare | bare | Cu | 6 |
| flexible | insulated-flexible | Cu | 0.75 |
| aerial | aerial | Cu | 6 |
| aerial | aerial | Al | 16 |