What size cable for a lighting circuit in NZ?

حاسبة مقاس الكابل

+2 references

Worked to AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

حجم الموصل

1.5mm²

السعة بعد الخفض
16A
هبوط الجهد
4.3%
موصل الأرضي
1.5mm²
فتح الحاسبة بهذه المدخلات

هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.

A drawn result card from the Cable Size tool: conductor size 1.5 mm²; voltage drop checked.

A lighting circuit on a 10 A breaker in New Zealand takes 1.5 mm² copper cable on a typical route. For 30 m of multicore PVC cable enclosed in air at 30 °C, the tool gives 16 A of derated capacity and a voltage drop of 4.3 %.

The case

The circuit is single‑phase at 230 V. The design current is the full 10 A of the curve C breaker. The voltage drop limit is 5 % and Ze is 0.35 Ω. Table 5.1 gives a 1.5 mm² earth, and the earth fault loop impedance is 1.34 Ω.

Voltage drop is the check closest to its limit. A longer run reaches the limit before the cable runs out of capacity.

What changes the answer

A 16 A lighting circuit on the same route takes 2.5 mm² with a drop of 3.76 %.

See also: How far can 1.5 mm² run on a 10 A circuit? and Voltage drop basics.

جرّبه بهذه المدخلات

درجة الحرارة المحيطة
30 °C
الأسلاك الداخلية
متعدد القلوب
منحنى الجهاز
المنحنى C
تحقق من جهاز الحماية
نعم
الدوائر المجمّعة
1
العزل
PVC 75 °C
طول المسار
30 m
تيار التصميم
10 A
المادة
النحاس
طريقة التركيب
Enclosed in air
معامل القدرة
1
الأطوار
طور واحد
القيمة الاسمية للجهاز
10 A
حد هبوط الجهد
5 %
الجهد
230 V
المعاوقة الخارجية Ze
0.35 Ω
فتح الحاسبة بهذه المدخلات

الخطوة التالية

المفاهيم التي تقوم عليه

أمثلة محلولة إضافية