Maximum Zs for a 16 A curve C breaker

Earth fault loop impedance calculator

+1 reference

Worked to AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Pinakamataas na pinapayagang Zs

1.92Ω

Earth fault loop impedance
0.89Ω
Pinakamahabang haba sa Zs
86.94m
Buksan ang calculator gamit ang mga input na ito

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

A drawn result card from the Loop Impedance tool: earth fault loop impedance 0.89 Ω; checked.

A 16 A curve C circuit breaker allows a maximum earth fault loop impedance of 1.92 Ω at 230 V. The tool reads it from AS/NZS 3000:2018 Table 8.1. A measured or calculated Zs at or below that value disconnects a fault in time.

The case

The circuit is 30 m of 2.5 mm² copper PVC cable with a 2.5 mm² earth, on a supply with Ze of 0.35 Ω. R1 + R2 is 0.54 Ω, so Zs is 0.89 Ω, well inside the limit. The longest run that still meets the limit is 86.94 m.

What changes the answer

The curve sets the limit. A 16 A curve B breaker trips at a lower multiple of its rating, so it allows 3.59 Ω, and the same cable can run 180.01 m.

A higher Ze shortens every run. Measure Ze at the board before you rely on a calculated Zs.

See also: AS/NZS 3000 Table 8.1 maximum Zs explained and Earth fault loop impedance and disconnection time.

Subukan gamit ang mga input na ito

Laki ng aktibong konduktor
2.5 mm²
Curve ng device
Curve C
Laki ng earth conductor
2.5 mm²
Insulation
PVC 75 °C
Standard
NZ · AS/NZS 3008.1.2
Haba ng run
30 m
Material
Tanso
Device rating
16 A
Voltage
230 V
External impedance Ze
0.35 Ω
Buksan ang calculator gamit ang mga input na ito

Ano ang susunod

Ang mga ideyang nasa likod nito

Higit pang worked example

Design aid ang AmpSize. I-verify ang mga resulta laban sa kasalukuyang standard.