How far can 1.5 mm² run on a 10 A circuit?

حاسبة أقصى طول للدائرة

+1 reference

Worked to AS/NZS 3000:2018. Tables checked 26 Sept 2026.

أقصى طول للمسار

34.85m

طول مسار حلقة العطل
82m
فحص التحكم
هبوط الجهد
فتح الحاسبة بهذه المدخلات

هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.

A drawn result card from the Maximum Circuit Length tool: maximum route length 34.85 m.

A 1.5 mm² copper circuit on a 10 A curve C breaker can run 34.85 m at its full load. Voltage drop sets that length: at 34.85 m the drop reaches the 5 % limit of AS/NZS 3000:2018 Cl 3.6.2.

The case

The circuit is single‑phase at 230 V with a 1.5 mm² earth and a design current of 10 A at a power factor of 1. AS/NZS 3000:2018 Table B1 gives a fault loop length of 82 m for this cable and device, so the loop is not the limit here.

What changes the answer

The real load is often lower than the breaker. A lighting circuit that draws less current can run further before the drop reaches the limit.

A larger cable runs further. 2.5 mm² on the same breaker reaches the limit at 63.82 m.

See also: What size cable for a lighting circuit in NZ? and Maximum length of a 20 A final subcircuit.

جرّبه بهذه المدخلات

الموصل الحي
1.5 mm²
تيار التصميم
10 A
جهاز الحماية
قاطع دائرة من النوع C
موصل الأرضي
1.5 mm²
العزل
PVC
الأطوار
طور واحد
معامل القدرة
1
القيمة الاسمية للجهاز
10 A
حد هبوط الجهد
5 %
جهد الطور الاسمي
230 V