تخطَّ إلى المحتوى
AmpSize

This page is not in العربية yet, so you are reading the English.

· قراءة 1 دقيقة

What size cable for a 22 kW EV charger?

حاسبة مقاس الكابل

+2 references

Worked to AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

حجم الموصل

6mm²

السعة بعد الخفض
38A
هبوط الجهد
1.04%
موصل الأرضي
2.5mm²
فتح الحاسبة بهذه المدخلات

هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.

A drawn result card from the Cable Size tool: conductor size 6 mm².

A 22 kW three‑phase EV charger on a 32 A circuit takes 6 mm² copper cable on a typical route. For 20 m of multicore PVC cable enclosed in air at 30 °C, the tool gives 38 A of derated capacity and a voltage drop of 1.04 %.

The case

At 400 V and unity power factor, a 22 kW charger draws 31.75 A in each phase. The circuit is sized for the full 32 A of its curve C breaker. Ze is 0.35 Ω and the voltage drop limit is 5 %. Table 5.1 gives a 2.5 mm² earth, and the earth fault loop impedance is 0.61 Ω.

What changes the answer

Length moves it. Over 60 m, the earth fault loop impedance sets the size, and the tool selects 10 mm² with a drop of 1.85 %.

The charger's circuit also needs its RCD and the spare capacity of the supply checked. The EV charger tool covers both.

See also: Three‑phase EV charger current and EV charger cable size for a 7 kW circuit.

جرّبه بهذه المدخلات

درجة الحرارة المحيطة
30 °C
الأسلاك الداخلية
متعدد القلوب
منحنى الجهاز
المنحنى C
تحقق من جهاز الحماية
نعم
الدوائر المجمّعة
1
العزل
PVC 75 °C
طول المسار
20 m
تيار التصميم
32 A
المادة
النحاس
طريقة التركيب
Enclosed in air
معامل القدرة
1
الأطوار
ثلاثي الأطوار
القيمة الاسمية للجهاز
32 A
حد هبوط الجهد
5 %
الجهد
400 V
المعاوقة الخارجية Ze
0.35 Ω
فتح الحاسبة بهذه المدخلات

الخطوة التالية

المفاهيم التي تقوم عليه

أمثلة محلولة إضافية

AmpSize أداة مساعدة للتصميم. تحقق من النتائج مقابل المعيار الحالي.

هل كان هذا مفيداً؟