UPS 容量与蓄电池运行时间
按运行时间为 UPS 及其蓄电池选型。
Reads AS/NZS 3000:2018. Tables checked 2 Oct 2026.
尝试一个工程 4
每项工作都会预填示例数值。请替换为您自己的数值。
- Size a UPS for a comms rackThe UPS and battery to keep a comms rack and security system up for half an hour.
- Find the battery for an hour on UPSHow much battery an office rack needs to run for an hour.
- Size a UPS for a small data hallA three‑phase UPS for forty racks for ten minutes, and its input current.
- Pick a UPS for a home officeThe UPS for a computer and router to ride a short outage.
输入
使用默认输入值的示例计算。
- UPS 上的负荷
- 3 行
- 增长裕量
- 25 %
- UPS 输出功率因数
- 0.9
- 电池运行时间
- 15 min
- 电池母线电压
- 96 V
- 电池供电时的逆变器效率
- 92 %
- 老化系数
- 1.25
- 充电时间
- 8 h
- 输入相数
- 单相
- 输入电压
- 230 V
- 市电供电时的 UPS 效率
- 94 %
- 输入功率因数
- 0.99
UPS 额定值,至少
1.86kVA
- 典型规格
- 2 kVA
- 负荷
- 1,340W
- 电池能量
- 455Wh
- 母线处的电池容量
- 4.7Ah
- 输入电流
- 6.5A
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 负荷,有功功率1,340W
- 负荷,视在功率1,424.6VA
- 计入 25 % 余量后负载所需的 kVA1.78kVA
- UPS 功率因数为 0.9 时,其千瓦数对应的 kVA1.86kVA
- UPS 额定值,至少结果1.86kVA
- 典型规格2 kVA
- 计入老化的 15 min 电池能量455Wh
- 96 V 下的电池容量4.7Ah
- 8 h 内充电时的输入功率1,488W
- 输入电流6.5A
关于此计算器
How this is calculated
A UPS has two sizes that matter: the power its inverter can deliver, and the energy its battery holds. This tool works both from a list of what the UPS supplies, then the current it draws from the supply.
You list each load with how many there are, the real power each draws in watts and its power factor. The tool adds the watts, and it adds each load's apparent power. With your headroom for growth on top, the UPS needs at least that many kVA, and its kW rating, its kVA times its output power factor, must cover the watts. The larger of the two is the rating. The tool also names the next typical size up; the sizes are common ratings, not a standard's list.
The battery must hold the load's watts for the run time, divided by the inverter's efficiency, times an ageing factor so it still lasts when old. Divided by the bus voltage that gives Ah, but at the run time's rate: a battery gives far less than its 10 or 20 hour Ah over a short run, so the maker's discharge table decides the battery.
The input is the load through the UPS's efficiency plus the power to recharge the battery in the time you set. AmpSize does not hold AS 62040, so the headroom, efficiencies and ageing factor are your assumptions. The result names the AS/NZS 3000 rules for converters.
| Step | Table or clause | What it decides |
|---|---|---|
| Load | Watts added, and each load's apparent power | The power the UPS supplies |
| Rating | The larger of the kVA and the kW at the output power factor | The UPS rating with headroom |
| Battery energy | Load times run time, over efficiency, times ageing | The energy at the battery bus |
| Battery capacity | Energy over the bus voltage, at the run time's rate | The Ah to look up in a maker's table |
| Input current | Load over efficiency, plus recharge | The current for the supply cable |
| Installation | AS/NZS 3000 Cl 4.12.4.2, Cl 4.12.5.1, Cl 4.12.5.2.2 and Cl 4.12.7 | The switch, protection, RCD and neutral rules |
Worked examples
- An office rack: two servers, three switches and storage, 15 min needs 1.86 kVA, so a 2 kVA unit, with 4.7 Ah at 96 V.
- The same rack for an hour still needs 1.86 kVA and a 2 kVA unit, but the battery holds 1,821 Wh.
- A comms rack and security system, 30 min on a 192 V battery needs 4.17 kVA, a 5 kVA unit, with 10.6 Ah at the bus.
- A small data hall of forty 1.2 kW racks, 10 min, three‑phase needs 61.86 kVA, an 80 kVA unit, drawing 76.6 A a phase.
- A home office PC and router, 10 min needs 0.51 kVA, so a 1 kVA unit.
Limits
The battery figure is the energy and Ah at the run time's rate. It does not pick cells: read the maker's constant-power discharge table at your end voltage and temperature. The tool does not model a UPS in parallel, redundancy such as N+1, the bypass supply, or a generator behind the UPS; for that, size the generator for the UPS's input.
See also: Generator sizing, Battery and Cable size.
问题
结果仅供设计参考。请依据现行标准核对。
如何进行 UPS 选型?
将其所供电所有设备的功率(W)及其 VA 相加,并预留增长余量。UPS 的 kVA 须能覆盖 VA 总量,其 kW 额定值(即 kVA 乘以输出功率因数)须能覆盖功率(W)总量。
运行时长需要多少蓄电池?
能量等于负荷功率(瓦)乘以时数,除以逆变器效率,再乘以老化系数。按母线电压换算为安时,取运行时间对应的放电速率,再查制造商的放电表。
为何 Ah 与蓄电池铭牌相差如此之大?
标签上标注的安时数是 10 或 20 小时的数值。在 15 分钟内,同一蓄电池提供的容量要少得多,因此 UPS 蓄电池应依据恒功率放电表选型,而非标签数值。
UPS 的供电电缆截面多大?
按输入电流选定规格:负荷经 UPS 效率折算后,加上为蓄电池充电所需的功率。本工具给出该电流,并将其带入电缆截面工具。
AS/NZS 3000 对 UPS 有什么规定?
Cl 4.12 适用于变流器,包括 UPS。旁路时至负荷的中性线保持连通,输出保护装置位于 15 m 范围内,蓄电池旁设置开关用于切断其供电。
本工具读取的条款和表格
- AS/NZS 3000:2018 Cl 4.12.4.2Switch for converter batteries
- AS/NZS 3000:2018 Cl 4.12.5.1Converter overcurrent protection
- AS/NZS 3000:2018 Cl 4.12.5.2.2RCDs on a converter output
- AS/NZS 3000:2018 Cl 4.12.7Neutral continuity through a UPS
- AS/NZS 3000:2018 Cl 4.12Electricity converters, including UPS