DC isolator rating for a 10 kW solar array

光伏隔离开关与接地计算器

+4 references

Worked to AS/NZS 5033:2021. Tables checked 1 Oct 2026.

A drawn result card from the PV Array Isolator and Earthing tool: 69.5 A at 550 V.

A domestic array has one d.c. isolator between the roof and the inverter. It must carry the array current, open under load and survive a fault. This guide rates that isolator with the PV isolator and earthing calculator. It also sizes the frame earth. The ideas are in PV array isolators and earthing.

The array

  • Four strings in parallel, each of modules with an Isc of 13.9 A. That is about a 10 kW array.
  • The string maximum voltage at the coldest cell is 550 V. The PV string tool gives it. See solar string sizing for a 600 V inverter.
  • A transformerless inverter, which is non‑separated. The array has no functional earth.
  • No string fuses. The isolator sits on the array cable, in the sun on the roof edge.
  • The inverter a.c. cable is 6 mm².

Step 1. Find the circuit currents

The maximum string current is 1.25 × 1 × 13.9 = 17.38 A. The other three strings can push 3 × 17.38 = 52.13 A back into one string. AS/NZS 5033:2021 Table 4.2 sets the string cable at 52.13 A and the array cable at 69.5 A.

Open the tool with this array.

Step 2. Set the isolator minimums

  • Voltage: at least 550 V (Cl 4.3.4.1).
  • Ithe: at least 69.5 A. The isolator is outdoors in the sun, so read Ithe at 60 °C (Cl 4.3.4.2.3).
  • Ie, the poles in series: at least 69.5 A.
  • Make and break: the inverter is non‑separated, so each pole must make and break 69.5 A (Table 4.3).

Ithe at 60 °C is lower than the 40 °C figure on most data sheets. Use the de-rating curve, not the headline number.

Step 3. Check a data sheet that passes

A switch-disconnector lists 1000 V, an Ithe of 80 A at 60 °C, an Ie of 70 A and a make and break of 80 A per pole.

Open the tool with these ratings. All four checks pass. The margins are 450 V, 10.5 A, 0.5 A and 10.5 A. The Ie margin is thin, so a slightly lower Ie would fail.

Step 4. Check a data sheet that fails per pole

A second switch lists the same voltage, Ithe and Ie. Its make and break is 40 A. On a transformerless inverter, the tool needs that figure per pole. It must reach 69.5 A, so the check fails by 29.5 A.

Open the tool with the failing switch. Pick a switch with a higher per-pole rating. Do not accept a figure that is lower than the array current.

Step 5. Size the frame earth

The array is above 35 V and the inverter is non‑separated with no fuses. Table 4.6 column (b)(i) takes the AS/NZS 3000 earth for the inverter a.c. active. A 6 mm² a.c. cable gives 2.5 mm² from Table 5.1. The least frame earth is 4 mm², so the earth is 4 mm². Keep the path to the installation earth at 0.5 Ω or less.

The tool also tells you to fit a pressure-equalisation valve to the outdoor enclosure, and an earth fault alarm, because the inverter is non‑separated.

The result

ItemValue
String cable current52.13 A
Array cable current69.5 A
Isolator Ithe at 60 °C, at least69.5 A at 550 V
Isolator Ie, at least69.5 A
Make and break per pole, at least69.5 A
Earth conductor, at least4 mm²

The tool does not size the cables. Size each one with the DC cable size tool at the current above.

使用这些输入试用

阵列最大电压
550 V
逆变器交流侧电缆规格
6 mm²
组件 Isc
13.9 A
隔离器位于
阵列电缆
隔离器接通和分断电流
80 A
隔离器 Ie,串联极数
70 A
环境温度下隔离器 Ithe
80 A
隔离器位置
室外,日晒处
隔离器电压额定值
1,000 V
KI,双面系数
1
逆变器
非隔离(无变压器)
并联组串
4
使用这些输入打开计算器

下一步

其背后的概念

更多示例

AmpSize 是设计辅助工具。请对照现行标准核实结果。

这是否有用?

有问题,或数值看起来有误?联系我们。