The cable size, correction factors and DC cable size tools read the ambient correction factor here. Table 3.44 gives the air factor and Table 3.45 the soil factor. Several factors differ from 2017.

已核验:对照印刷版标准阅读,页码 84–85。检查于 27 Sept 2026。

单位:Temp °C

这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。

返回 AS/NZS 3008.1.1:2025 页面上的对应卡片

41 行

Table 3.44, 3.45, Correction factors for ambient air and soil temperature
InsulationMediumConductor temp CTemp (°C)Factor
PVCair75151.31
PVCair75201.25
PVCair75251.2
PVCair75301.13
PVCair75351.07
PVCair75401
PVCair75450.93
PVCair75500.85
PVCair75550.76
PVCair75600.65
PVCair75650.53
PVCair75700.38
XLPEair90151.22
XLPEair90201.18
XLPEair90251.14
XLPEair90301.1
XLPEair90351.05
XLPEair90401
XLPEair90450.95
XLPEair90500.89
XLPEair90550.84
XLPEair90600.77
XLPEair90650.71
XLPEair90700.63
XLPEair90750.55
XLPEair90800.45
XLPEair90850.32
PVCsoil75101.14
PVCsoil75151.1
PVCsoil75201.05
PVCsoil75251
PVCsoil75300.95
PVCsoil75350.89
PVCsoil75400.84
XLPEsoil90101.11
XLPEsoil90151.07
XLPEsoil90201.04
XLPEsoil90251
XLPEsoil90300.96
XLPEsoil90350.92
XLPEsoil90400.88