跳至内容
AmpSize

AS/NZS 3000:2018

Cl 4.4.2.2, Cl 4.7 and Cl 4.18

Where socket‑outlets, switches and other accessories may not go: floors, cooktops and gas

The accessory location tool reads the floor, cooktop and gas distances: 75 mm, 150 mm and 2.5 m, the Figure 4.18 cylinder areas, the Figure 4.19 vent zones and the Figure 4.20 regulator zone.

已核验:对照印刷版标准阅读,页码 225, 243–245, 261–264 (PDF = page + 4)。检查于 1 Oct 2026。

单位:Value mm mm, A mm mm, B mm mm, Top mm mm, L M m, D M m, R M m

这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。

返回 AS/NZS 3000:2018 页面上的对应卡片

13 行

Cl 4.4.2.2, Cl 4.7 and Cl 4.18, Where socket-outlets, switches and other accessories may not go: floors, cooktops and gas
KindJurisdictionValue mmClausePageA mmB mmTop mmMax vent mmL M (m)D M (m)R M (m)ScaleMax pressure kpaHeight mmRadius mm
limitboth754.4.2.2(b)225
limitboth1504.7.3244
limitboth25004.7.3244
noteboth20004.7.1244
dutyboth—4.7.1244
dutyboth—4.7.1244
zoneboth4.18.2.12625001500500
zoneboth4.18.2.126215003500500
dutynz—4.18.2.3262
dutynz—4.18.3262
zoneboth4.18.4263501.510.5—200
zoneboth4.18.4263—1.510.5T200
zonenz4.18.52641600800