Whakawhiti ki te ihirangi
AmpSize

Tātaitai rahi taura

Tātaitai rahi taura kore utu mō Aotearoa me Ahitereiria. Ka pānui i AS/NZS 3008.1.2:2017, i AS/NZS 3008.1.1:2025 rānei me te 2017 ka kōwhiria, ā, ka arotake i AS/NZS 3000.

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Whakamātau mahi 24

Ka whakakī ia mahi i ngā uara tauira. Whakakapia ērā ki ō uara.

Ngā whakauru

He tauira mahi me ngā whakauru taunoa.

Ngā wāhanga
Wāhanga toru
Voltage
400 V
Iahiko hoahoa
50 A
Power factor
0.9
Paerewa
NZ · AS/NZS 3008.1.2
Roa rerenga
60 m
Tikanga whakaurunga
Kua kōpakina ki te hau
Pāmahana taiao
30 °C
Ngā ara iahiko whakarōpū
1
Ihinga harmonic tuatoru
0 %
Rauemi
Parahi
Insulation
PVC 75 °C
Ngā matua
Multicore
Ngā waea i te whakarite
1
Rohe heke voltage
5 %
Tirohia te taputapu tiaki
Kāo
Iahiko hapa ka puta pea
0 kA

Rahi kaikawe

10mm²

Kaha kua whakaiti
50A
Heke voltage
2.66%
Kaikawe whenua
4mm²
Tauwehe whakaheke katoa
1.00

He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.

Ngā hīkoi tātaitanga

  1. Tauutu whakaheke pāmahana taiao×1.00

    AS/NZS 3008.1.2:2017 Tables 27(1), 27(2) p.88

  2. Tauwehe whakaheke whakarōpū×1.00

    One circuit, no grouping factor

  3. Tauwehe whakaiti oneone×1.00

    AS/NZS 3008.1.2:2017 Table 29 p.90

  4. Tauutu whakaheke hōhonu tanu×1.00

    AS/NZS 3008.1.2:2017 Tables 28(1), 28(2) p.89

  5. Tauwhāinga whakaiti katoa×1.00
  6. Au ripanga e hiahiatia ana50A

    AS/NZS 3000:2018 Cl 3.4

  7. Rahi kaikawe kua kōwhiriaHua10mm²

    AS/NZS 3008.1.2:2017 Table 13 p.62–64

  8. Kaha au whakaheke50A

    AS/NZS 3000:2018 Cl 3.4

  9. Heke whakahiato2.66%

Mō tēnei tātaitai

How this is calculated

The tool tests every standard conductor size in turn. It reports the smallest size that passes each check you ask for.

  1. Tabulated current. It reads the current each size can carry for your material, insulation, core count and installation method. The Standard select decides which part it reads. It reads AS/NZS 3008.1.2:2017 for New Zealand or AS/NZS 3008.1.1 for Australia. For Australia, the Edition select picks 2025 or the superseded 2017 edition.
  2. Correction factors. It multiplies the ambient, grouping, soil, burial depth and harmonic factors into one correction factor (derating factor in 2017). It divides the design current by that factor. Above 33 % third harmonic, it uses the neutral current instead. The result is the current the cable must carry in the table.
  3. Voltage drop. It works out the drop for the run length, the power factor and the conductor. It compares the drop with the limit you set. The default limit is 5 %.
  4. Protective device. If you name a device, its rating must sit at or below the derated capacity. The circuit's earth fault loop impedance must stay under the maximum for that device.
  5. Fault withstand. If you enter a prospective fault current, the conductor must withstand it for the clearing time. The k factor sets that limit. It depends on the material, the insulation and the conductor size.
  6. Result. The tool lists each size that fails and the check it failed. Each step names its table or clause where one applies.
StepTable or clauseWhat it decides
Current ratingTable 13 or 14 for multicore, Tables 4, 5, 7 and 8 for single coreThe current each size carries in your installation method
AmbientTables 27(1) and 27(2)The correction factor for the air or soil temperature
GroupingTables 22, 25(1) and 25(2)The correction factor for circuits run together
Buried cableTable 29, Tables 28(1) and 28(2)The correction factors for soil resistivity and depth
HarmonicsTable 2 and Cl 3.5.9The reduction for third harmonic current in the neutral
Required currentAS/NZS 3000 Cl 3.4The current the cable must carry after correction
Voltage dropTables 30, 34 and 35, Cl 4.5, AS/NZS 3000 Cl 3.6.2The drop over the run and the limit it must meet
DeviceAS/NZS 3000 Cl 2.5.3.1That the rating sits between the design current and the capacity
Earth and ZsAS/NZS 3000 Table 5.1 and Table 8.1The earth conductor size and the maximum loop impedance
Fault withstandTable 52 and Cl 5.3The k factor and the smallest size that survives the fault

Tables without a standard named are in the part of AS/NZS 3008.1 you pick. AS/NZS 3008.1.1:2025 numbers them by section, such as Table 3.18 for Table 13.

Common circuits, worked with the tool

Each line states its route. Change one input and the size can change, so run your own circuit before you buy cable. Every line uses multicore copper with PVC insulation and one circuit on the route. The power factor is 0.9, except where a line names a different value. Ze is 0.35 Ω and every size uses the New Zealand tables.

New Zealand and Australia

The Standard select picks the part of AS/NZS 3008.1 the tool reads. Part 1.2 holds the New Zealand tables. They assume 30 °C air and 15 °C soil. Part 1.1 holds the Australian tables. They assume 40 °C air and 25 °C soil. The checks from AS/NZS 3000 are the same in both countries.

For Australia, the Edition select picks AS/NZS 3008.1.1:2025 or the superseded 2017 edition. A new calculation starts on 2025. A link with no edition reads 2017, so an old link keeps its numbers.

A single‑phase circuit at 32 A runs 25 m on the 2025 Australian edition. It sits enclosed in air at 40 °C, grouped with one other circuit. It needs 10 mm² with a derated capacity of 35.2 A. Open the Australian example.

A three‑phase circuit at 30 A and 400 V runs 30 m, buried direct in soil at 25 °C. On the 2025 edition it needs 2.5 mm² with a derated capacity of 34 A. The 2017 edition gives 4 mm² with a derated capacity of 33 A. Open it on 2025 or on 2017.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

See also: Cable size for a 32 A single‑phase 25 m run, EV charger cable size for a 7 kW 32 A circuit and Current-carrying capacity and derating.

Pātai

He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.

He rahi taura pēhea me whai au mō tētahi ara iahiko 32 A i NZ?

10 mm² parahi i runga i tētahi ara tauira. He ara iahiko wāhanga kotahi, 32 A, 25 m te roa. Kua kōpakina, i te hau 35 °C, ā, kua whakarōpūtia me tētahi atu ara iahiko kotahi. Ko tōna kaha kua whakaitihia (derated) he 37.6 A, ā, ko te heke voltage he 1.42 %. He rerekē te otinga mō tētahi ara rerekē, nō reira whakaurua ō ake uara.

Ka taea e tētahi taura 6 mm² te kawe i te 40 A?

Ehara i te ara tauira. Ka roa te ara 20 m mō te 40 A wāhanga kotahi, kua kōpakina ki te hau i te 30 °C. I runga i taua ara, ka hinga te parahi 6 mm² i te arotake kaha kawe iahiko. Ka kōwhiri te taputapu i te 10 mm², me te 50 A o te kaha derating. Kāore e panoni tērā e te ara poto ake, nā te mea ko te ara te mea e whakatau ana i te kaha, ehara i te roa.

He rahi taura pēhea mō tētahi submain wāhanga toru 63 A?

25 mm² parahi i tēnei ara, me te kaha derating 95 A. E 35 m te roa, 63 A, 400 V, XLPE, kua kāpehia ki te hau i 35 °C. Ko te taputapu he C curve 63 A, ā, he 0.3 Ω te Ze. E whakatutuki ana te 16 mm² i ngā arotake iahiko me te heke, engari kāore ia e whakatutuki i Table 8.1 i tōna loop impedance 0.49 Ω.

Ka mahi te tātaitai rahi taura mō Ahitereiria?

Āe. Whakatakotoria te Standard ki AU · AS/NZS 3008.1.1. Ka kōwhiri te Edition i AS/NZS 3008.1.1:2025, ko te taunoa, i te putanga 2017 kua whakakahoretia rānei. Kōwhiria te 2017 hei whakahou i tētahi hoahoa tawhito. Ka whakamahia e ngā putanga e rua te hau 40 °C me te oneone 25 °C. Ko NZ · AS/NZS 3008.1.2 te Standard taunoa. Ko ngā tātari AS/NZS 3000, he mea tuhi ai ko AS3000 te ingoa, he ōrite i ngā whenua e rua.

Ko ēhea ngā ripanga AS/NZS 3008 e whakamahia ana e te tātaitai Rahi Taura?

I raro i AS/NZS 3008.1.2:2017 me 3008.1.1:2017, ka ahu mai ngā reiti single‑core i ngā Tables 4, 5, 7 me 8, ā, ko ngā multicore i 13 me 14. Ko te derating i ngā Tables 22 me 25 ki 29, ko te impedance i ngā Tables 30 ki 35, ko te k i Table 52. Ka whakahou anō a AS/NZS 3008.1.1:2025 i ia tau, nā reira ko Table 13 ko 3.18. Ka hoatu a AS/NZS 3000:2018 Tables 5.1 me 8.1 i te rahi whenua me te Zs nui rawa.

Ngā tauira mahi

Ngā aratohu 24 katoa mō tēnei tātaitai

Kōrero o muri

Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu

Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi

Ngā tūtohi i arotakehia whakamutunga i te 27 Sept 2026.

He whai hua tēnei?

He pātai, he uara rānei e kitea ana he hē? Whakapā mai.