Values of constant K for determination of permissible short-circuit currents

This table gives one flat k factor per material and insulation. The cable size and fault rating tools read Table 52 from the short-circuit limits table instead. There, the k factor depends on the temperature limits Tables 53 and 55 set.

Kua manatokotia: pānuitia ki te paerewa tā, whārangi 121–122. I tirohia 19 Sept 2026.

Ngā unit: K A·s^0.5/mm2

Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.

Hoki ki tana kāri i te whārangi AS/NZS 3008.1.2:2017

4 rārangi

Table 52, Values of constant K for determination of permissible short-circuit currents
MaterialInsulationInitial temp CFinal temp CK (A·s^0.5/mm2)
CuPVC75160111
CuXLPE90250143
AlPVC7516073.6
AlXLPE9025094.5