跳至内容
AmpSize

AS/NZS 3000:2018

Table C6, C7

Simplified protective device selection for 1 to 25 mm² cables

The simplified selector reads the largest protective device rating Tables C6 and C7 allow for a conductor size. It reads one for each installation condition the tables separate, for circuits of one phase and of three.

已核验:对照印刷版标准阅读,页码 478–479。检查于 26 Sept 2026。

单位:Size mm2, Rating A

这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。

返回 AS/NZS 3000:2018 页面上的对应卡片

16 行

Table C6, C7, Simplified protective device selection for 1 to 25 mm² cables
PhasesSize (mm2)In air unenclosedThermal insulation partialThermal insulation completeIn air enclosedIn ground enclosed
11161081316
11.52016101620
12.52520162032
143225202540
164032253250
1106350325063
1168063406380
125100805080100
31131061316
31.5161381620
32.52016102025
343220162532
364032203240
3105040254050
3166350326363
3258063408080

读取它的工具 (1)