AS/NZS 3000:2018
Table C3
Maximum demand, energy demand method for non‑domestic installations
The floor area demand tool reads the VA/m² range and average for each use. It takes no figure from the special equipment rows, which print none.
Na-verify: binasa laban sa naka-print na standard, mga pahina 473–474 (PDF 477–478). Na-check noong 1 Oct 2026.
Mga unit: Min va VA/m², Max va VA/m², Avg va VA/m²
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
20 na row
| Occupancy | Use | Min va (VA/m²) | Max va (VA/m²) | Avg va (VA/m²) | Ev | Total |
|---|---|---|---|---|---|---|
| Offices | Light and power | 40 | 60 | 50 | ||
| Offices | Airconditioning, cooling | 30 | 40 | 35 | ||
| Offices | Airconditioning, reverse cycle | 20 | 30 | 25 | ||
| Offices | Airconditioning, zonal reheat | 40 | 60 | 50 | ||
| Offices | Airconditioning, variable volume | 20 | 20 | 20 | ||
| Carparks | Open air | 0 | 10 | 5 | ||
| Carparks | Open air, EV charging | 5 | 15 | 10 | yes | |
| Carparks | Basement | 10 | 20 | 15 | ||
| Carparks | Basement, EV charging | 10 | 30 | 20 | yes | |
| Retail shops | Light and power | 40 | 100 | 70 | ||
| Retail shops | Airconditioning | 20 | 40 | 30 | ||
| Warehouses | Light and power | 5 | 15 | 10 | ||
| Warehouses | Ventilation | 5 | 5 | 5 | ||
| Warehouses | Special equipment | — | — | — | ||
| Light industrial | Light and power | 10 | 20 | 15 | ||
| Light industrial | Ventilation | 10 | 20 | 15 | ||
| Light industrial | Airconditioning | 30 | 50 | 40 | ||
| Light industrial | Special equipment | — | — | — | ||
| Taverns, licensed clubs | Total | 60 | 100 | 80 | yes | |
| Theatres | Total | 80 | 120 | 100 | yes |