How far can 1.5 mm² run on a 10 A circuit?

Maximum circuit length calculator

+1 reference

Worked to AS/NZS 3000:2018. Tables checked 26 Sept 2026.

Pinakamahabang haba ng ruta

34.85m

Haba ng ruta ng fault loop
82m
Governing check
Voltage drop
Buksan ang calculator gamit ang mga input na ito

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

A drawn result card from the Maximum Circuit Length tool: maximum route length 34.85 m.

A 1.5 mm² copper circuit on a 10 A curve C breaker can run 34.85 m at its full load. Voltage drop sets that length: at 34.85 m the drop reaches the 5 % limit of AS/NZS 3000:2018 Cl 3.6.2.

The case

The circuit is single‑phase at 230 V with a 1.5 mm² earth and a design current of 10 A at a power factor of 1. AS/NZS 3000:2018 Table B1 gives a fault loop length of 82 m for this cable and device, so the loop is not the limit here.

What changes the answer

The real load is often lower than the breaker. A lighting circuit that draws less current can run further before the drop reaches the limit.

A larger cable runs further. 2.5 mm² on the same breaker reaches the limit at 63.82 m.

See also: What size cable for a lighting circuit in NZ? and Maximum length of a 20 A final subcircuit.

Subukan gamit ang mga input na ito

Active conductor
1.5 mm²
Design current
10 A
Protective device
Type C circuit-breaker
Earth conductor
1.5 mm²
Insulation
PVC
Mga phase
Single phase
Power factor
1
Device rating
10 A
Limit ng voltage drop
5 %
Nominal phase voltage
230 V
Buksan ang calculator gamit ang mga input na ito

Ano ang susunod

Ang mga ideyang nasa likod nito

Higit pang worked example

Design aid ang AmpSize. I-verify ang mga resulta laban sa kasalukuyang standard.