AS/NZS 3008.1.1:2017
Table 2
Reduction factors for harmonic currents in 4- and 5‑core cables
With the AU standard, the correction factors tool reads the third harmonic reduction factor here. The values print the same as the New Zealand part.
Na-verify: binasa laban sa naka-print na standard, mga pahina 27–28. Na-check noong 19 Sept 2026.
Mga unit: Third harmonic percent %, Factor x
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
4 na row
| Band | Min percent | Max percent | Factor (x) | Basis |
|---|---|---|---|---|
| 0–15 % | 0 | 15 | 1 | phase |
| 15–33 % | 15 | 33 | 0.86 | phase |
| 33–45 % | 33 | 45 | 0.86 | neutral |
| > 45 % | 45 | 1 | neutral |