AS/NZS 3000:2018
Table 3.7
Minimum separation of underground services
The underground cable tool reads the minimum separation from other underground services, such as gas, water and telecommunications.
Na-verify: binasa laban sa naka-print na standard, mga pahina 203. Na-check noong 26 Sept 2026.
Mga unit: Separation mm mm, Electrode mm mm
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
6 na row
| Service | Separation mm | Electrode mm |
|---|---|---|
| water-le-dn65 | 100 | 500 |
| water-gt-dn65 | 300 | 500 |
| sanitary-drainage | 100 | 500 |
| stormwater-drainage | 100 | 600 |
| gas | 100 | 500 |
| telecommunications | 100 | — |