DC isolator rating for a 10 kW solar array

حاسبة مفتاح عزل PV والتأريض

+4 references

Worked to AS/NZS 5033:2021. Tables checked 1 Oct 2026.

A drawn result card from the PV Array Isolator and Earthing tool: 69.5 A at 550 V.

A domestic array has one d.c. isolator between the roof and the inverter. It must carry the array current, open under load and survive a fault. This guide rates that isolator with the PV isolator and earthing calculator. It also sizes the frame earth. The ideas are in PV array isolators and earthing.

The array

  • Four strings in parallel, each of modules with an Isc of 13.9 A. That is about a 10 kW array.
  • The string maximum voltage at the coldest cell is 550 V. The PV string tool gives it. See solar string sizing for a 600 V inverter.
  • A transformerless inverter, which is non‑separated. The array has no functional earth.
  • No string fuses. The isolator sits on the array cable, in the sun on the roof edge.
  • The inverter a.c. cable is 6 mm².

Step 1. Find the circuit currents

The maximum string current is 1.25 × 1 × 13.9 = 17.38 A. The other three strings can push 3 × 17.38 = 52.13 A back into one string. AS/NZS 5033:2021 Table 4.2 sets the string cable at 52.13 A and the array cable at 69.5 A.

Open the tool with this array.

Step 2. Set the isolator minimums

  • Voltage: at least 550 V (Cl 4.3.4.1).
  • Ithe: at least 69.5 A. The isolator is outdoors in the sun, so read Ithe at 60 °C (Cl 4.3.4.2.3).
  • Ie, the poles in series: at least 69.5 A.
  • Make and break: the inverter is non‑separated, so each pole must make and break 69.5 A (Table 4.3).

Ithe at 60 °C is lower than the 40 °C figure on most data sheets. Use the de-rating curve, not the headline number.

Step 3. Check a data sheet that passes

A switch-disconnector lists 1000 V, an Ithe of 80 A at 60 °C, an Ie of 70 A and a make and break of 80 A per pole.

Open the tool with these ratings. All four checks pass. The margins are 450 V, 10.5 A, 0.5 A and 10.5 A. The Ie margin is thin, so a slightly lower Ie would fail.

Step 4. Check a data sheet that fails per pole

A second switch lists the same voltage, Ithe and Ie. Its make and break is 40 A. On a transformerless inverter, the tool needs that figure per pole. It must reach 69.5 A, so the check fails by 29.5 A.

Open the tool with the failing switch. Pick a switch with a higher per-pole rating. Do not accept a figure that is lower than the array current.

Step 5. Size the frame earth

The array is above 35 V and the inverter is non‑separated with no fuses. Table 4.6 column (b)(i) takes the AS/NZS 3000 earth for the inverter a.c. active. A 6 mm² a.c. cable gives 2.5 mm² from Table 5.1. The least frame earth is 4 mm², so the earth is 4 mm². Keep the path to the installation earth at 0.5 Ω or less.

The tool also tells you to fit a pressure-equalisation valve to the outdoor enclosure, and an earth fault alarm, because the inverter is non‑separated.

The result

ItemValue
String cable current52.13 A
Array cable current69.5 A
Isolator Ithe at 60 °C, at least69.5 A at 550 V
Isolator Ie, at least69.5 A
Make and break per pole, at least69.5 A
Earth conductor, at least4 mm²

The tool does not size the cables. Size each one with the DC cable size tool at the current above.

جرّبه بهذه المدخلات

الجهد الأقصى للمصفوفة
550 V
حجم كابل التيار المتردد للعاكس
6 mm²
Isc للوحدة
13.9 A
العازل عند
كابل المصفوفة
تيار الوصل والفصل للعازل
80 A
Ie للعازل، أقطاب على التوالي
70 A
Ithe للعازل عند درجة الحرارة المحيطة
80 A
موقع العازل
في الهواء الطلق، في الشمس
تصنيف جهد العازل
1,000 V
KI، معامل ثنائي الوجه
1
عاكس
غير معزول (بدون محول)
السلاسل المتوازية
4
فتح الحاسبة بهذه المدخلات

الخطوة التالية

المفاهيم التي تقوم عليه

أمثلة محلولة إضافية

AmpSize أداة مساعدة للتصميم. تحقق من النتائج مقابل المعيار الحالي.

هل كان هذا مفيداً؟

سؤال، أو قيمة تبدو خاطئة؟ اتصل بنا.