跳至内容
AmpSize

变压器励磁涌流及其断路器

检查变压器合闸励磁涌流与其断路器的配合。

Reads AS/NZS 3000:2018. Tables checked 2 Oct 2026.

输入

使用默认输入值的示例计算。

额定值
15 kVA
相
三相
一次侧电压
400 V
二次侧电压
400 V
二次侧回路
一个,本身无保护
涌流,× 满载电流
12
涌流持续时间
0.1 s
断路器类型
C 型曲线
额定值
32 A

合闸时的断路器

可能跳闸

涌入电流
259.8A
一次侧满载电流
21.65A
能容纳的最小 Type B
100 A
能容纳的最小 Type C
63 A
能容纳的最小 Type D
32 A
二次导体,至少
21.7A

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. 一次侧满载电流21.65A
  2. 涌流,为满载电流的 12 倍,持续 0.1 s259.8A
  3. C 32 A 型,典型瞬动带宽下限160A
  4. C 32 A 型,典型瞬动带宽上限320A
  5. 合闸时的断路器结果可能跳闸
  6. 能容纳的最小 Type B100 A
  7. 能容纳的最小 Type C63 A
  8. 能容纳的最小 Type D32 A
  9. 二次导体,至少21.7A

    AS/NZS 3000:2018 Cl 4.14.2.2

关于此计算器

How this is calculated

When a transformer is switched on, its core can draw a large current for a few cycles while the magnetic flux settles. This inrush can be ten or more times the full load current. It lasts about a tenth of a second, and it is often enough to trip the breaker on the primary. This tool checks whether it does, and finds a breaker that rides through it.

The tool takes the primary full load current from the transformer tool, then multiplies it by the inrush multiple you enter, for the time you enter. No standard on hand prints these two figures, so they are your assumptions. Take them from the maker's data sheet. The multiple is a peak, and the tool compares it with the breaker's band, which is given in RMS multiples of the rating, as if it were RMS: that errs towards a trip.

It then places that current on the trip band of the breaker, the same band the MCB trip curve tool draws. The breaker holds when the band's earliest trip is no sooner than the inrush lasts. It trips when the latest trip is sooner, and it may trip in between. For each type, B, C and D, the tool finds the smallest rating that carries the full load current and holds.

With one circuit on the secondary and no protection there, AS/NZS 3000 lets the secondary cable go without its own breaker if it carries the primary current scaled by the voltage ratio. The tool gives that current.

StepTable or clauseWhat it decides
Full load currentThe transformer toolThe current the inrush multiplies
InrushThe multiple and time you enterThe current and time the breaker sees
The breaker's bandAS/NZS 3000 Cl 2.5.3.1 and Table 8.1, and a typical bandHolds, may trip or trips
The secondary cableAS/NZS 3000 Cl 4.14.2.2 ExceptionThe least capacity of an unprotected secondary cable
An extra-low voltage transformerAS/NZS 3000 Cl 4.14.1 Exception 2Whether Cl 4.14 applies at all

Worked examples

Limits

The inrush depends on where on the wave the transformer is switched and on the flux left in the core, so it differs from one switch-on to the next. The tool uses one figure for the peak and one for the time. A toroidal transformer can draw much more than a laminated one. A soft-start or inrush limiter changes the figures; enter what the maker gives.

The breaker's band is typical of its type, not a maker's curve. The tool does not check a fuse or a moulded-case breaker.

See also: MCB trip curve, Transformer and Cable size.

问题

结果仅供设计参考。请依据现行标准核对。

变压器合闸时为何跳开断路器?

铁芯在数个周波内会产生较大的励磁电流,直至磁通稳定。涌流可达满载电流的十倍或更多。若涌流进入断路器的瞬动区,断路器可能跳闸。

变压器励磁涌流有多大?

这取决于设计以及合闸时的波形位置。约 0.1 s 内为满载电流的 10 至 12 倍是常用的初步估计。环形变压器的涌流可能更大。实际数值以制造商的数据手册为准。

哪种断路器曲线适合变压器?

通常为 D 型,其典型瞬动区从额定值的 10 倍开始。对于相同的涌流,C 型需要更大的额定值,B 型则需要更大。工具会找出能满足要求的每种类型的最小额定值。

二次侧电缆是否需要独立的断路器?

AS/NZS 3000 Cl 4.14.2.2 允许单个未设保护的二次侧回路不设保护,前提是其电缆能承载一次侧额定电流乘以一、二次侧电压比。回路数量增加时,每个回路均须设置保护。

断路器的脱扣带是否即制造商的曲线?

否。这是该类型的典型区间,与 MCB 脱扣曲线工具所绘制的区间相同。若结果为“可能跳闸”,请核对制造商曲线,或选择更大一级的额定值。

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 2 Oct 2026。

这是否有用?

有问题,或数值看起来有误?联系我们。