MCB 脱扣曲线与电缆限值
将 MCB 脱扣带与其所保护的电缆绘制在一起。
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 2 Oct 2026.
尝试一个工程 4
每项工作都会预填示例数值。请替换为您自己的数值。
- Check a breaker clears a long circuitA long lighting run with little fault current against its breaker and cable.
- See a D curve on a motor circuitHow long a D curve breaker can take at a modest fault, against the cable.
- Check a small cable near the boardWhether a high fault current outruns a small cable before the breaker trips.
- Compare a B and C curve breakerThe instant trip current of a Type B breaker on a socket‑outlet circuit.
输入
使用默认输入值的示例计算。
- 断路器类型
- C 型曲线
- 额定值
- 20 A
- 末端故障电流
- 300 A
- 配电板处的故障电流
- 0 A
- 标准
- NZ · AS/NZS 3008.1.2
- 电缆截面
- 2.5 mm²
- 材料
- 铜
- 绝缘
- PVC 75 °C
故障电流下的最迟脱扣时间
0.1s
- 故障电流下的电缆耐受
- 0.86s
- 瞬时脱扣,Table 8.1 依据
- 150A
- 瞬时脱扣,典型范围
- 100 至 200A
- 约定动作电流
- 29A
- 0.4 s 时的最大 Zs
- 1.53Ω
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 约定动作电流29A
AS/NZS 3000:2018 Cl 2.5.3.1
- 平均跳闸电流,Type C150A
AS/NZS 3000:2018 Table 8.1
- 平均值时的瞬时脱扣,不超过0.1s
AS/NZS 3000:2018 Table 8.1
- 0.4 s 时的最大 Zs1.53Ω
AS/NZS 3000:2018 Table 8.1
- 典型瞬动带宽,下限100A
- 典型瞬动带宽,上限200A
- k 系数×111.00
AS/NZS 3008.1.2:2017 Table 52 p.121
- 故障电流下的电缆耐受0.86s
AS/NZS 3008.1.2:2017 Cl 5.3
- 故障电流下的最迟脱扣时间结果0.1s
关于此计算器
How this is calculated
A miniature circuit-breaker does not trip at one exact time for a current. Two breakers of the same type and rating trip at different times, so a maker draws a band: the earliest and the latest each can trip. This tool draws that band for a Type B, C or D breaker, draws the cable's limit beside it, and reads the latest trip time at the fault current you enter.
Three figures come from AS/NZS 3000. A breaker operates within its conventional time at 1.45 times its rating. Table 8.1 takes it as tripping instantly, within 0.1 s, at its mean tripping current: 4 times the rating for Type B, 7.5 for Type C and 12.5 for Type D. The largest loop impedance for a 0.4 s disconnection follows from that current. The rest of the band, the edges of the instant region and the thermal part, is a typical band. AmpSize does not hold AS/NZS 60898, and the result says so.
The cable's line is its adiabatic limit: the time it can carry a fault current before its insulation is damaged, from the k factor of AS/NZS 3008.1, through the fault rating tool. The circuit passes when the breaker's latest time is no longer than the cable's time at that current. Check it at the far end, where the fault current is least and the trip slowest, and give the fault current at the board too: there the current is highest, the cable's time shortest, and the worse of the two ends decides.
| Step | Table or clause | What it decides |
|---|---|---|
| Conventional operating current | AS/NZS 3000 Cl 2.5.3.1 | Where the band starts |
| Instant trip at the mean current | AS/NZS 3000 Table 8.1 and Para B4.5 | The current that trips it instantly, and the largest Zs |
| Instant region and thermal edges | A typical band, not a standard | The earliest and latest trip at each current |
| The cable's limit | AS/NZS 3008.1 Table 52 and Cl 5.3 | The time the cable withstands the fault |
| The check | The latest trip against the cable's time | Whether the breaker clears the fault first |
Worked examples
- A C20 lighting circuit in 2.5 mm² with a 300 A fault trips in 0.1 s at the latest, well inside the cable's 0.86 s. The Table 8.1 instant trip current is 150 A.
- A B20 circuit in 2.5 mm² with a 150 A fault trips in 0.1 s against the cable's 3.42 s. The Table 8.1 instant trip current is 80 A.
- A D32 motor circuit in 6 mm² with a 500 A fault can take up to 1.6 s on the slow edge of the band, just inside the cable's 1.77 s. Table 8.1 counts it as instant above 400 A.
- A long B16 circuit in 1.5 mm² with only 60 A of fault current fails: the breaker can take 27.74 s, longer than the cable's 7.7 s, and 60 A is under the Table 8.1 instant trip current of 64 A.
- The same C20 circuit with 3000 A of fault at the board fails at the board: the band shows 0.1 s there, and the cable lasts 0.01 s at 3000 A, though it takes 0.86 s at the far end's 300 A. The maker's let-through energy decides it.
- A C32 circuit in 4 mm² close to the board, 2000 A of fault fails on the band: it shows 0.1 s, and the cable lasts 0.05 s. The maker's let-through energy decides it.
Limits
The band is typical, not a maker's curve. A real breaker clears a large fault in much less than 0.1 s, and limits the energy it lets through; the maker publishes that energy as I²t. Where the band fails a cable at a high current, compare the maker's I²t with k²S² before you change the cable.
gG fuses are not drawn yet. Their curves are in IEC 60269, which AmpSize does not hold.
See also: Loop impedance, Fault rating and IDMT protection.
问题
结果仅供设计参考。请依据现行标准核对。
B、C 和 D 曲线 MCB 有什么区别?
多大电流会使其瞬时跳闸。AS/NZS 3000 Table 8.1 取平均值:B 型为额定值的 4 倍,C 型为 7.5 倍,D 型为 12.5 倍。较高型号可躲过电动机和变压器启动。
为何动作曲线绘制为一条带状区域?
同一型号、同一额定值的两个断路器,跳闸时间可能不同。制造商给出各自可能的最早和最晚跳闸时间。本工具采用最晚时间,因此检查结论对最慢的断路器同样成立。
如何确认断路器能在故障时保护电缆?
电缆在由其 k 系数和截面决定的时间内可承受故障电流,即 (k × S ÷ I)²。断路器必须在该时间内动作。工具在您输入的故障电流下对两者进行比较。
该区间是否即制造商的曲线?
否。动作点数据来自 AS/NZS 3000,而区间边界为该类型的典型值。AmpSize 未收录 AS/NZS 60898。若结果接近临界,请在制造商曲线上核对。
若电缆持续时间少于 0.1 s 怎么办?
在配电箱附近,故障电流较大,而小截面电缆仅能承受几毫秒。断路器可在 0.1 s 之内切断大故障电流。请将制造商的通过能量 I²t 与 k²S² 比较。
本工具读取的条款和表格
- AS/NZS 3000:2018 Cl 2.5.3.1Operating points of circuit-breakers and fuses
- AS/NZS 3000:2018 Table 8.1Maximum earth fault loop impedance multipliers by MCB curve
- AS/NZS 3008.1.2:2017 Table 52Values of constant K for determination of permissible short-circuit currents
- AS/NZS 3008.1.2:2017 Table 52, 53, 54, 55Short-circuit K values and temperature limits
- AS/NZS 3008.1.1:2017 Table 52Values of constant K for determination of permissible short-circuit currents
- AS/NZS 3008.1.1:2017 Table 52, 53, 54, 55Short-circuit K values and temperature limits
- AS/NZS 3008.1.1:2025 Table 5.1Values of constant K for determination of permissible short-circuit currents
- AS/NZS 3008.1.1:2025 Table 5.1, 5.2, 5.3, 5.4Short-circuit K values and temperature limits
表格最后核对于 2 Oct 2026。