蓄电池位置检查器
依据 AS/NZS 5139,检查家用储能电池可以安装在哪里。
Reads AS/NZS 5139:2019. Tables checked 1 Oct 2026.
尝试一个工程 4
每项工作都会预填示例数值。请替换为您自己的数值。
- Check a battery beside a hot water unitA garage battery 450 mm from the hot water cylinder.
- Check a battery on a bedroom wallThe barrier an outdoor battery needs on a weatherboard wall to a bedroom.
- Check a battery in a corridorThe egress width left past a battery in an apartment corridor.
- Check the working space at a batteryA 700 mm space against the maker’s 1 m clearance.
输入
使用默认输入值的示例计算。
- 电池类型
- 一体化(预装集成式 BESS)
- 位置
- 车库
- 电池 IP 代码
- IP55
- Distance to the nearest exit
- 1,500 mm
- Distance to a window or vent
- 0 mm
- Distance to an appliance
- 800 mm
- 其上方的出口、窗户或电器
- 否
- 墙面,靠近居住用房间
- 否
- Gap to the ceiling
- 1,100 mm
- 建筑物设有火灾指示盘
- 否
- Working space in front
- 1,000 mm
- 面板连接至 230 V 交流接线点
- 是
- Maker’s clearance
- 0 mm
AS/NZS 5139 第 4 节
满足 9 条规则中的 8 条
- 符合规则
- 8
- 不符合规则
- 0
- 未评估
- 1
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 至出口、窗户或通风口,或至设备的净空,不小于600mm
AS/NZS 5139:2019 Cl 4.2.2.2
- 在上述物品下方至少留出的净空900mm
AS/NZS 5139:2019 Cl 4.2.2.2(e)
- 室内 IP 代码,不低于IP2X
AS/NZS 5139:2019 Cl 4.2.3.2
- 工作空间,至少900mm
AS/NZS 5139:2019 Cl 4.2.5
关于此计算器
How this is calculated
The tool checks a site for an all-in-one home battery. It reads AS/NZS 5139:2019 Section 4. It shows each rule as met, not met or not assessed. A distance you leave blank stays not assessed.
- Place. It tests the location against the restricted places (Cl 4.2.2.2(a) to (k)). These are switchboard-restricted places, ceiling spaces, wall cavities, roofs unless deemed suitable, under stairways or access walkways, and escape routes. They also include habitable rooms of homes and hazardous areas.
- Clearances. It compares your distances to an exit, a window or vent of a habitable room, and another appliance with the 600 mm rule. An item above the battery needs the 900 mm rule. In a corridor it checks the 1 m left for egress (Cl 4.2.2.1).
- IP code. It wants IP2X indoors and IP23 outdoors (Cl 4.2.3.2). It compares each digit of your code.
- Barrier. If the battery is on a wall to a habitable room, the wall must be non‑combustible (Cl 4.2.4.2). On a combustible wall, a non‑combustible barrier must reach 600 mm past each side, 900 mm above and down to the bottom.
- Ceiling. If the ceiling is within 900 mm of the top, it must be non‑combustible for 600 mm past the battery (Cl 4.2.4.2).
- Working space. It wants 600 mm on the working side, or 900 mm where panels reach the 230 V a.c. connections. It takes the maker's figure if that is larger (Cl 4.2.5).
- Notes. It adds notes for a smoke alarm or fire panel detector (Cl 4.3.4, a "should") and for the maker's ventilation instructions (Cl 4.3.5).
| Check | Clause | What it decides |
|---|---|---|
| Location | Cl 4.2.2.2 | Whether the place is restricted |
| Exit, window, appliance | Cl 4.2.2.2 | The side and below clearances |
| Corridor | Cl 4.2.2.1 | The width left for egress |
| IP rating | Cl 4.2.3.2 | The least enclosure rating |
| Barrier | Cl 4.2.4.2 | The non‑combustible wall behind the battery |
| Ceiling | Cl 4.2.4.2 | The non‑combustible ceiling above it |
| Working space | Cl 4.2.5 | The clear space to work in |
Worked example
- A garage wall that backs onto a bedroom. The tool gives 4 of 9 rules not met: the appliance clearance, the barrier, the ceiling and the working space. The hot water unit is 400 mm away. The barrier reaches 300 mm each side and 500 mm above. The ceiling is 700 mm over the battery. The working space is 700 mm.
- The same wall, fixed. The tool gives 9 of 9 rules met.
Limits
- The tool covers a pre-assembled integrated BESS, Section 4. It does not assess other battery types. AmpSize does not hold Sections 5 and 6.
- AmpSize does not hold Amendment 1 (2025). Check it for changes.
- The tool tests the numbers you enter. It does not know your site. A roof needs a check that it is deemed suitable.
- It does not size the battery, the cable or the protection.
See also: Home battery location and clearances, Where can a home battery go, Solar battery size for a family home and the home battery tool.
问题
结果仅供设计参考。请依据现行标准核对。
家用储能电池不得安装在哪里?
AS/NZS 5139:2019 Cl 4.2.2.2 规定一体式蓄电池不得设于居住房间、吊顶空间、墙体空腔、楼梯或走道下方空间、疏散通道及危险区域。仅在被认定为适宜的情况下,允许设于屋顶。
蓄电池距门、窗或热水器须多远?
距居住房间的出口、窗户或通风口,或距热水器、空调等其他电器的侧向距离至少为 600 mm。同时,其位置须比上述任一项至少低 900 mm。
蓄电池可以安装在卧室的墙上吗?
是的,前提是墙体为不燃材料,例如砖、混凝土、水泥板或瓷砖。若为可燃墙体,须加装不燃隔板,两侧各超出 600 mm,上方高出 900 mm。900 mm 范围内的天花板也需同样处理。
蓄电池前方需要多大空间?
工作侧至少 600 mm;若配电箱面板触及 230 V 交流接线,则至少 900 mm。制造商要求更大时,本工具取较大值。
本工具是否涵盖所有蓄电池?
本工具涵盖一体式家用储能电池,即 AS/NZS 5139 的 Section 4。AmpSize 未收录其他系统的 Section 5 和 Section 6 规则,也未收录 Amendment 1(2025)。本工具会明确说明,而不作猜测。
计算示例
背景
本工具读取的条款和表格
- AS/NZS 5139:2019 Cl 4.2.2.2Restricted locations for a home battery
- AS/NZS 5139:2019 Cl 4.2.3.1Battery location by risk assessment
- AS/NZS 5139:2019 Cl 4.2.3.2IP rating of a home battery
- AS/NZS 5139:2019 Cl 4.2.4.2Barrier to a habitable room
- AS/NZS 5139:2019 Cl 4.2.5Working space at a home battery
- AS/NZS 5139:2019 Cl 4.3.4Smoke alarm or detector at a home battery
- AS/NZS 5139:2019 Cl 4.3.5Ventilation of a home battery
- AS/NZS 5139:2019 Cl 4.2.2 to 4.2.5Location, clearance and barrier rules for a pre-assembled integrated BESS
表格最后核对于 1 Oct 2026。