Maximum route lengths for conductor sizes and protective devices
The maximum circuit length tool reads the route length Table B1 allows for a conductor pair and a protective device, for a 0.4 s disconnection time at 230 V. A pair the table does not print has no tabulated length.
已核验:对照印刷版标准阅读,页码 452–453。检查于 26 Sept 2026。
单位:Active mm², Earth mm², Rating A A, Type B m, Type C m, Type D m, Fuse m
这些是 AmpSize 所编码的数值。不转载标准原文。请依据现行标准核对。
20 行
| Active (mm²) | Earth (mm²) | Rating A | Type B (m) | Type C (m) | Type D (m) | Fuse (m) |
|---|---|---|---|---|---|---|
| 1 | 1 | 6 | 170 | 91 | 55 | 204 |
| 1 | 1 | 10 | 102 | 55 | 33 | 114 |
| 1.5 | 1.5 | 10 | 153 | 82 | 49 | 170 |
| 1.5 | 1.5 | 16 | 96 | 51 | 31 | 82 |
| 2.5 | 2.5 | 16 | 160 | 85 | 51 | 136 |
| 2.5 | 2.5 | 20 | 128 | 68 | 41 | 93 |
| 4 | 2.5 | 25 | 126 | 67 | 40 | 90 |
| 4 | 2.5 | 32 | 98 | 52 | 31 | 70 |
| 6 | 2.5 | 40 | 90 | 48 | 29 | 60 |
| 10 | 4 | 50 | 117 | 62 | 37 | 73 |
| 16 | 6 | 63 | 142 | 76 | 45 | 85 |
| 16 | 6 | 80 | 112 | 59 | 36 | 59 |
| 25 | 6 | 80 | 124 | 66 | 40 | 66 |
| 25 | 6 | 100 | 99 | 53 | 32 | 47 |
| 35 | 10 | 100 | 159 | 85 | 51 | 75 |
| 35 | 10 | 125 | 127 | 68 | 41 | 58 |
| 50 | 16 | 125 | 198 | 106 | 63 | 90 |
| 50 | 16 | 160 | 155 | 83 | 50 | 71 |
| 70 | 25 | 160 | 235 | 126 | 75 | 108 |
| 70 | 25 | 200 | 188 | 100 | 60 | 84 |