B1

Maximum route lengths for conductor sizes and protective devices

The maximum circuit length tool reads the route length Table B1 allows for a conductor pair and a protective device, for a 0.4 s disconnection time at 230 V. A pair the table does not print has no tabulated length.

Na-verify: binasa laban sa naka-print na standard, mga pahina 452–453. Na-check noong 26 Sept 2026.

Mga unit: Active mm², Earth mm², Rating A A, Type B m, Type C m, Type D m, Fuse m

Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.

Bumalik sa card nito sa page ng AS/NZS 3000:2018

20 na row

B1, Maximum route lengths for conductor sizes and protective devices
Active (mm²)Earth (mm²)Rating AType B (m)Type C (m)Type D (m)Fuse (m)
1161709155204
11101025533114
1.51.5101538249170
1.51.51696513182
2.52.5161608551136
2.52.520128684193
42.525126674090
42.53298523170
62.54090482960
10450117623773
16663142764585
16680112593659
25680124664066
25610099533247
3510100159855175
3510125127684158
50161251981066390
5016160155835071
702516023512675108
70252001881006084