Maximum Zs for a 16 A curve C breaker

حاسبة معاوقة حلقة عطل التأريض

+1 reference

Worked to AS/NZS 3000:2018. Tables checked 27 Sept 2026.

أقصى Zs مسموح

1.92Ω

معاوقة حلقة عطل التأريض
0.89Ω
أقصى طول عند Zs
86.94m
فتح الحاسبة بهذه المدخلات

هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.

A drawn result card from the Loop Impedance tool: earth fault loop impedance 0.89 Ω; checked.

A 16 A curve C circuit breaker allows a maximum earth fault loop impedance of 1.92 Ω at 230 V. The tool reads it from AS/NZS 3000:2018 Table 8.1. A measured or calculated Zs at or below that value disconnects a fault in time.

The case

The circuit is 30 m of 2.5 mm² copper PVC cable with a 2.5 mm² earth, on a supply with Ze of 0.35 Ω. R1 + R2 is 0.54 Ω, so Zs is 0.89 Ω, well inside the limit. The longest run that still meets the limit is 86.94 m.

What changes the answer

The curve sets the limit. A 16 A curve B breaker trips at a lower multiple of its rating, so it allows 3.59 Ω, and the same cable can run 180.01 m.

A higher Ze shortens every run. Measure Ze at the board before you rely on a calculated Zs.

See also: AS/NZS 3000 Table 8.1 maximum Zs explained and Earth fault loop impedance and disconnection time.

جرّبه بهذه المدخلات

مقاس الموصل الحي
2.5 mm²
منحنى الجهاز
المنحنى C
مقاس موصل التأريض
2.5 mm²
العزل
PVC 75 °C
المعيار
NZ · AS/NZS 3008.1.2
طول المسار
30 m
المادة
النحاس
القيمة الاسمية للجهاز
16 A
الجهد
230 V
المعاوقة الخارجية Ze
0.35 Ω
فتح الحاسبة بهذه المدخلات

الخطوة التالية

المفاهيم التي تقوم عليه

أمثلة محلولة إضافية