Whakataurite tikanga tīmatanga mōtā
Whakatairitea ngā tīmatanga DOL, star-delta, soft start me te drive.
Whakamātau mahi 4
Ka whakakī ia mahi i ngā uara tauira. Whakakapia ērā ki ō uara.
- Compare starters for a centrifugal pumpStart current and torque of six methods for a 15 kW pump.
- Check star-delta on a loaded conveyorWhich starts a 22 kW conveyor that needs high breakaway torque.
- Estimate the dip of a fan startThe voltage dip of each method for a 37 kW fan.
- Start a bore pump on a weak supplyThe dip of a 5.5 kW pump at the end of a rural line.
Ngā whakauru
He tauira mahi me ngā whakauru taunoa.
- Pūngao tahanga
- 11 kW
- Voltage raina
- 400 V
- Power factor
- 0.85
- Pai
- 0.9
- Iahiko rotor kua aukatia
- 6 x
- Torque rotor arokore
- 200 %
- Te taiurutanga whakawehe utu
- 30 %
- Tapu autotransformer
- 65 %
- Ōkiko tuatahi, whakahiato i te mōtā
- 70 %
- Rohe au a te kaitīmata māeneene
- 3.5 x
- Rohe au o te kaiwhakahaere
- 150 %
- Taumata hapa i te mōto
- 0 kA
Te au tīmatanga iti rawa e tīmata ai te utu
Variable speed drive
- Iahiko Uta Katoa
- 20.75A
- Au tīmata, DOL
- 124.5A
- Te au tīmatanga, te tikanga kua kōwhiria
- 31.13A
- Te taiurutanga tīmatanga, te tikanga kua kōwhiria
- 150%
He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.
Ngā hīkoi tātaitanga
- Au utanga katoa20.75A
Induction motor at standstill: current with the voltage, torque with its square.
- Hurihuri utanga katoa72.2Nm
- Au rotor aukati124.5A
- Hurihuri rotor aukati200%
- Hurihuri whakawehe utanga30%
- Au tīmata, Direct on line124.5A
- Taimana tīmata, Direct on line200%
- Au tīmata, Star-delta41.5A
- Taimana tīmata, Star-delta66.7%
- Au tīmata, Autotransformer52.6A
- Taimana tīmata, Autotransformer84.5%
- Au tīmata, Primary resistance87.15A
- Taimana tīmata, Primary resistance98%
- Au tīmata, Soft starter72.63A
- Taimana tīmata, Soft starter68.1%
- Au tīmata, Variable speed drive31.13A
- Taimana tīmata, Variable speed drive150%
Mō tēnei tātaitai
How this is calculated
You give the motor's shaft power, line voltage, power factor and efficiency. The tool works the full load current and full load torque the same way the motor tool does. Then you give the locked-rotor current and torque from the motor data, and the torque the load needs to break away from rest.
A cage induction motor at standstill behaves like a transformer with its secondary shorted. Its current follows the voltage at its terminals, and its torque follows the square of that voltage. Every starting method is a way of lowering the voltage at the motor, or of controlling the current directly. So the tool scales the locked-rotor current and torque for each method:
- direct on line takes the full locked-rotor current and torque;
- star-delta puts the line voltage divided by the square root of 3 across each winding, so the line current and the torque both fall to a third;
- an autotransformer at a tap gives the motor the tap voltage; the motor current falls with the tap, the line current and the torque with the tap squared;
- primary resistance leaves part of the voltage at the motor; the current falls with it, the torque with its square;
- a soft starter holds the current at its limit, and the torque falls with the square of that limit over the locked-rotor current;
- a drive starts at rated flux, so its torque follows its current limit.
A method starts the load where its starting torque is above the breakaway torque. With a fault level at the motor terminals, the tool estimates the dip as the starting current over the fault current.
| Step | Table or clause | What it decides |
|---|---|---|
| Full load current and torque | The motor tool's method | The base for every multiple |
| Direct on line | Locked-rotor data | The highest current and torque |
| Star-delta | One third of each | The current and torque in star |
| Autotransformer and primary resistance | Voltage ratio and its square | The current and torque at the tap |
| Soft starter and drive | Current limit | The current and torque each allows |
| Starts the load | Breakaway torque | Which methods start it |
Worked examples
- An 11 kW centrifugal pump. Every method starts it. Direct on line draws 124.5 A and star-delta 41.5 A. The lowest start that still turns the pump is the variable speed drive, at 31.13 A.
- A 22 kW loaded conveyor. Star-delta gives 73.3 % torque against a 120 % load, so it cannot start the belt. The lowest start that does is direct on line, at 290.57 A.
- A 37 kW fan on a board with 6 kA. The dip is 8.1 % direct on line and 2.7 % in star-delta. The lowest start is the variable speed drive, at 104.72 A and a 1.7 % dip.
- A 5.5 kW bore pump at the end of a rural line. Direct on line dips the supply 9.1 %, a soft starter at 3.5 times full load current 4.5 %. The lowest start is the variable speed drive, at 15.57 A.
Limits
The comparison is at standstill. It does not follow the torque through the run-up, so a star-delta start that breaks the load away can still stall before the change to delta. The drive figures assume rated flux; the supply side of a drive draws less than the motor side at low speed. The dip is an estimate for comparing methods, not a flicker study. Choose the circuit-breaker so its magnetic trip clears the starting current of the method used, and set the overload to the full load current.
See also: Motor starting methods: current and torque, Starting a loaded conveyor and Motor.
Pātai
He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.
Ka pēhea te whakaiti a star-delta i te iahiko tīmata?
Ki te hautoru o te iahiko direct on line, nā te mea ka whiwhi ia wiriwiri i te voltage raina kua wehea ki te pūtakerua o te 3 i te tīmatanga. Ka heke hoki te torque tīmata ki te hautoru.
Ka tīmata te star-delta i tōku uta?
Ka taea anake ina tuatoru o te torque locked-rotor kei runga ake i te torque wehe uta. Ka tīmata pea he pūkaha, he pamu centrifugal; ko te kaitāwhiri uta, te kaikākāti pea kāore pea. Ka tohu te taputapu i ia tikanga e tīmata ana i te uta.
He aha te mahi a te tap autotransformer?
I tētahi tap 65 %, ka kite te mōtā i te 65 % o te voltage. Ka heke te iahiko mōtā me te torque i te tap, ā, ka heke te iahiko raina i te tap tapawhā, nā reira ka tango te tap 65 % i te 42 % pea o te iahiko direct on line.
He aha te drive e tango iti rawa ai i te iahiko i te tīmatanga?
Ka tīmata te drive i te mōtā i te auau iti me te flux whakatauhia, nā reira ka hoatu te torque uta katoa i te iahiko uta katoa pea. Ka whakamahia e te taputapu te rohe iahiko o te drive hei iahiko tīmata me te torque.
Me pēhea te tātai i te voltage dip?
Ko te iahiko tīmata ka whakawehea ki te iahiko hapa ka puta pea ki ngā pou mōtā. He tatauranga tēnei e whakaaro ana ki te puna me te tīmata i te power factor ōrite. Whakamahia hei whakataurite tikanga, ehara hei rangahau flicker.
Ngā tauira mahi
Kōrero o muri
Ngā taputapu hononga
- Rahi generator mai i tētahi Rārangi UtaSize a generator from a load list with motor starting.Kāore he paerewa
- Tātaitai mōtāFind motor full load current, starting current and torque.Kāore he paerewa
- Tātaitai ara iahiko mōtāCable, breaker, contactor and overload for one motor.AS/NZS 3000AS/NZS 3008.1.2AS/NZS 3008.1.1