Công cụ tính phụ tải cực đại theo diện tích sàn
Ước tính phụ tải thương mại theo diện tích sàn và mục đích sử dụng.
Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.
Thử một công việc 4
Mỗi công việc điền sẵn giá trị ví dụ. Hãy thay bằng giá trị của bạn.
- Estimate demand for a shop by floor areaThe demand of a 600 m² shop with airconditioning, from Table C3.
- Estimate demand for a warehouseA 3000 m² warehouse with ventilation and 40 kVA of special equipment.
- Estimate demand for a basement carparkA 4000 m² basement carpark with EV charging on a quarter of it.
- Estimate demand for an office floorAn 800 m² office with reverse cycle air, at the top of the range.
Dữ liệu nhập
Ví dụ tính toán với dữ liệu nhập mặc định.
- Các pha
- Ba pha
- Điện áp pha
- 230 V
- Giá trị lấy từ bảng
- Giá trị trung bình in
- Các khu vực
- 2 hàng
- Thiết bị đặc biệt
- 0 kVA
Nhu cầu tối đa trên mỗi pha
217.39A
- Tổng nhu cầu
- 150kVA
- Offices · Light and power
- 75kVA
- Offices · Airconditioning, zonal reheat
- 75kVA
Kết quả này là công cụ hỗ trợ thiết kế. Hãy kiểm tra theo tiêu chuẩn hiện hành.
Các bước tính toán
- Số liệu lấy từ Bảng C3Trung bình in trên nhãn
AS/NZS 3000:2018 Table C3
- Offices · Light and power, nhu cầu năng lượng50VA/m²
AS/NZS 3000:2018 Table C3
- Offices · Light and power, 1500 m²75kVA
AS/NZS 3000:2018 Table C3
- Offices · Airconditioning, zonal reheat, nhu cầu năng lượng50VA/m²
AS/NZS 3000:2018 Table C3
- Offices · Airconditioning, zonal reheat, 1500 m²75kVA
AS/NZS 3000:2018 Table C3
- Nhu cầu tổng150kVA
AS/NZS 3000:2018 App C Para C2.4.3
- Dòng trên mỗi pha, kVA ÷ (3 × điện áp pha)Kết quả217.39A
AS/NZS 3000:2018 App C Para C2.4.3
Giới thiệu công cụ tính này
How this is calculated
The tool estimates the maximum demand of a commercial or light-industrial building from its floor area. It uses the energy demand method in AS/NZS 3000:2018 App C Para C2.4.3. It reads the VA per square metre from Table C3.
- Pick the figure. For each area, choose an occupancy and a use. The tool takes the printed average, or the low or high end of the printed range (Table C3). You can type your own figure instead.
- Work out each area. The tool multiplies the area by the VA per square metre and divides by 1000. The result is kVA.
- Add EV charging. The NOTE to Table C3 puts EV charging on top of all other energy demands. The tool adds the carpark EV rows to the total.
- Add special equipment. Table C3 prints no figure for it. You enter its kVA from the load details, and the tool adds it.
- Total demand. The tool adds every area and the special equipment (Para C2.4.3).
- Current. On one phase, the tool divides the kVA by the phase voltage. On three phases, it divides by 3 times the phase voltage. That gives the current in each phase.
| Step | Table or clause | What it decides |
|---|---|---|
| Figure per area | Table C3 | The VA per square metre for each use |
| EV charging | NOTE to Table C3 | The charging load added on top |
| Total demand | App C Para C2.4.3 | The sum of the areas and special equipment |
| Current | App C Para C2.4.3 | The demand in amps on each phase |
Worked example
- Small retail and office building with basement EV charging. Shops of 600 m² at 70 VA/m² for light and power and 30 VA/m² for air conditioning. Offices of 400 m² at 50 and 25 VA/m². A basement carpark of 300 m² at 15 VA/m², plus its EV charging at 20 VA/m². The total demand is 100.5 kVA. The current is 145.65 A per phase at 230 V.
- The Paragraph C2.4.3.2 case. 1500 m² of office at 50 + 50 VA/m². The total demand is 150 kVA. The current is 217.39 A per phase.
Limits
- Table C3 is for commercial and light-industrial buildings. It is not for homes. Use Table C1 for a home.
- The figures depend on the climate, the hours of use, energy management and how evenly the load spreads.
- The per phase figure assumes an even spread over three phases. Check the heaviest phase where the load is uneven.
- The tool uses the phase voltage. On a 230/400 V supply, enter 230.
- Special equipment has no printed figure. You must know its kVA. The tool does not guess it.
- An own figure outside the printed range gives a warning. Check it before you rely on it.
- To work from a list of loads, use the Table C2 method in the Maximum Demand tool.
See also: The energy demand method and Table C3, Shop and office maximum demand by floor area and the Maximum Demand tool.
Câu hỏi
Kết quả chỉ là công cụ hỗ trợ thiết kế. Đối chiếu với tiêu chuẩn hiện hành.
Khi nào tôi dùng Table C3 thay vì Table C2?
Table C3 phù hợp với tòa nhà thương mại hoặc công nghiệp nhẹ ở giai đoạn thiết kế sơ bộ, khi bạn biết diện tích sàn và công năng nhưng chưa biết phụ tải. Table C2 cần các nhóm phụ tải. Khi đã biết phụ tải, hãy kiểm tra phụ tải tính toán theo Table C2.
Tôi nên lấy số liệu nào trong dải?
Công cụ mở ở mức trung bình đã in. Tiêu chuẩn nêu rằng số liệu phụ thuộc vào khí hậu, số giờ, quản lý năng lượng và mức độ phân bố đều của phụ tải. Hãy chọn mức cao cho khí hậu nóng hoặc số giờ dài, hoặc nhập số liệu riêng của bạn.
Công cụ đổi kVA ra ampe như thế nào?
Công cụ chia tổng VA cho điện áp pha. Với ba pha, công cụ chia cho ba lần điện áp pha, nên 150 kVA ở 230 V cho 217.39 A mỗi pha. Kết quả này khớp với ví dụ trong Paragraph C2.4.3.2.
Sạc xe điện có nằm trong con số bãi đỗ xe không?
Không. Table C3 liệt kê sạc xe điện thành một dòng riêng dưới mục bãi đỗ ngoài trời và bãi đỗ tầng hầm, và NOTE của bảng xếp nó cộng thêm vào mọi phụ tải khác. Hãy cộng thêm khu vực sạc xe điện bên cạnh khu vực bãi đỗ.
Còn thiết bị đặc biệt trong kho hoặc xưởng thì sao?
Table C3 không in số liệu cho thiết bị đặc biệt. Hãy tính từ chi tiết phụ tải và nhập theo kVA. Công cụ sẽ cộng vào tổng.
Các điều khoản và bảng mà công cụ này đọc
- AS/NZS 3000:2018 App C Para C2.4.3Energy demand method for commercial installations
- AS/NZS 3000:2018 Table C3Maximum demand, energy demand method for non‑domestic installations
Mọi điều khoản và bảng, kèm cách mỗi mục đã được kiểm chứng
Các bảng được kiểm tra lần cuối ngày 1 Oct 2026.
Công cụ liên quan
- Công cụ tính phụ tải cực đạiEstimate maximum demand for domestic or non‑domestic loads.AS/NZS 3000 Table C1/C2
- Công cụ tính phụ tải cực đại theo phaSpread the load over three phases and see the imbalance.AS/NZS 3000
- Công cụ tính dung lượng dự phòngSee if a new load fits the main switch of a supply.AS/NZS 3000 Cl 2.2.2
Thông tin này có hữu ích không?