Harmonics, Iahiko Neutral me te k factor
THD, Iahiko Neutral me te k factor mai i tētahi spectrum.
Reads AS/NZS 3000:2018, AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3008.1.1:2017 (AU). Tables checked 2 Oct 2026.
Whakamātau mahi 4
Ka whakakī ia mahi i ngā uara tauira. Whakakapia ērā ki ō uara.
- Find the harmonic neutral current of an officeThe neutral current of an office floor full of computers, from its spectrum.
- Find the K-factor for a drive transformerThe K-factor of six-pulse drives, for the transformer that feeds them.
- Check an LED lighting circuit for harmonicsWhether a cable for LED drivers is picked on its neutral current.
- Neutral current with some electronic loadThe neutral of a board where electronics are 30 % of the load.
Ngā whakauru
He tauira mahi me ngā whakauru taunoa.
- Rōhe whakahaere
- NZ · AS/NZS 3008.1.2
- Au wāhanga, rms tūturu
- 100 A
- Third harmonic
- 35 %
- Fifth harmonic
- 20 %
- Seventh harmonic
- 10 %
- Ninth harmonic
- 5 %
- Eleventh harmonic
- 4 %
- Thirteenth harmonic
- 3 %
- Fifteenth harmonic
- 2 %
- Wāhanga o te kawenga wāhanga e hanga ana i ngā harmonics
- 100 %
- Au kāore i taurite
- 0 A
Te neutral triplen
97.88A
- Te whakaroa harmonic katoa o te au
- 42.18%
- Te tauwehe-K
- 3.59
- Te tauwehe whakaiti Table 2
- ×0.86
- Taura kua kōwhiria
- Te au wae
- Te au hei kōwhiri i te taura
- 116.28A
- Cl 3.5.2(b)(i) iti rawa mō te neutral
- 38.86A
He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.
Ngā hīkoi tātaitanga
- Te whakaroa harmonic katoa o te au42.18%
- Te au matua92.14A
- Harmonic triplen, √(h3² + h9² + h15²)35.41%
- Te neutral triplenHua97.88A
- Harmonic tuatoru, paiheneti o te au wāhanga32.25%
AS/NZS 3008.1.2:2017 Table 2
- Te tauwehe whakaiti Table 2×0.86
AS/NZS 3008.1.2:2017 Table 2
- Au neutral mai i te harmonic tuatoru anake96.75A
AS/NZS 3008.1.2:2017 Cl 3.5.9
- Te au hei kōwhiri i te taura116.28A
AS/NZS 3008.1.2:2017 Cl 3.5.9
- Au harmonic o tētahi wae, te tuatoru me ngā mea ake38.86A
- Cl 3.5.2(b)(i) iti rawa mō te neutral38.86A
AS/NZS 3000:2018 Cl 3.5.2(b)(i)
- Te tauwehe-K3.59
Mō tēnei tātaitai
How this is calculated
Electronic loads draw current in pulses, not as a smooth wave. A power quality analyser splits that current into the fundamental and its harmonics, each shown as a percent of the fundamental. The tool takes the true rms phase current and that spectrum, from the third to the fifteenth order.
The total harmonic distortion is the rms of all the harmonic percents. The fundamental current is the rms current divided by the square root of one plus the distortion squared.
The third, ninth and fifteenth harmonics are the triplens. In the three phases they are in step, so they add in the neutral instead of cancelling. With equal phases the neutral carries three times one phase's triplen current. That is the tool's main answer.
AS/NZS 3008.1 Table 2 bands the third harmonic as a percent of the phase current. So the tool converts the analyser's percent of the fundamental to a percent of the rms current. It reads the band through the cable size tool's own path, and gives the reduction factor, whether the cable is picked on the phase or the neutral current, and the current to carry to cable size.
AS/NZS 3000 Cl 3.5.2(b)(i) gives a minimum for the neutral of a substantial harmonic load: the out-of-balance current plus one phase's harmonic current. Size the neutral for the larger of it and the triplen figure. AmpSize reads the harmonic current as the rms of the third and higher orders. Note 1 sets what substantial means.
The K-factor weights each harmonic by its order squared, because eddy current loss in a transformer rises with frequency squared. A clean load gives 1.
| Step | Table or clause | What it decides |
|---|---|---|
| Distortion | The rms of the harmonic percents | The THD and the fundamental current |
| Triplen neutral | Three times one phase's triplens | The neutral current of three equal phases |
| Third harmonic band | Table 2 | The reduction factor and the basis the cable is picked on |
| Neutral of the third harmonic | Cl 3.5.9 | The current the cable is picked on above the middle band |
| Clause neutral | Cl 3.5.2(b)(i) | The out-of-balance current plus one phase's harmonic current |
| Substantial load | Cl 3.5.2(b)(i) Note 1 | Whether the clause figure applies |
| K-factor | Each order squared, weighted by its share | The transformer K rating to pick at or above |
Worked examples
- An office floor of 80 A with 40 % third harmonic puts 87.16 A in the neutral, more than a phase. The current has 49.34 % THD and a K-factor of 4.37.
- Six-pulse drives drawing 150 A put only 13.43 A in the neutral, as their harmonics are mostly fifth and seventh. The current has 35.14 % THD and a K-factor of 5.12.
- An LED lighting circuit of 40 A puts 64.28 A in the neutral. The current has 89.16 % THD and a K-factor of 10.01.
- A 60 A board where electronics are 30 % of the load puts 58.73 A of triplens in the neutral if every load had this spectrum. The current has 42.18 % THD and a K-factor of 3.59. Below 40 % the clause figure does not apply.
Limits
The tool assumes three equal phases with the same spectrum. A real board has a mix. Enter the worst phase's readings for a safe answer.
It does not work voltage distortion, resonance with power factor capacitors or filter design. Those need the supply's impedance and a harmonic study.
See also: Neutral current, Cable size and Transformer.
Pātai
He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.
Me pēhea te tātai i te iahiko neutral harmonic?
Ko ngā harmonics tuatoru, tuaiwa me te tekau mā rima o ngā wāhanga toru e rite ana te tū, nō reira ka tāpiri ki te neutral. Ina ōrite ngā wāhanga, ka kawe te neutral i te toru ngā mea o te triplen current o tētahi wāhanga kotahi. Ka mahia e te taputapu mai i te iahiko wāhanga me te spectrum.
He aha te THD o te iahiko?
Ko te distortion harmonic katoa te rms o ngā iahiko harmonic katoa i runga i te fundamental, hei ōrau. Ka whakaatu tētahi analyser i ia raupapa hei ōrau o te fundamental. Ka tango te taputapu i era, ā, ka hoatu i te THD me te iahiko fundamental.
He aha te k factor?
Ka taumahatia e ia ia harmonic ki tōna raupapa tapawhā, nā te mea ka piki te ngaronga eddy current i tētahi transformer ki te auau tapawhā. Ko tētahi uta mā ko K-1. Kōwhiria he reiti K transformer e tū ana i runga rānei i te tauanga. Kāore ngā hīkoi reiti i roto i tētahi paerewa e pupuri ana a AmpSize.
Āhea ka pā te rahi taura ki te Iahiko Neutral?
Ka wehea e AS/NZS 3008.1 Table 2 te harmonic tuatoru hei ōrau o te iahiko wāhanga. Ki runga ake i te 33 % ka kōwhiria te taura mai i te iahiko neutral. Ka hoatu e te taputapu te tauwehe, te tūāpapa me te iahiko hei kawe mō te rahi taura.
He aha tā AS/NZS 3000 e tono ana mō tētahi uta harmonic?
Ka tāpiri a Cl 3.5.2(b)(i) i te iahiko harmonic tuatoru, ake atu i te iahiko kore taurite mō te neutral, ka tango i te 100 % o te iahiko harmonic o te wāhanga teitei rawa. Ka kī a Note 1 he nui te uta harmonic o te 40 % neke atu o te uta o tētahi wāhanga.
Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu
- AS/NZS 3000:2018 Cl 3.5.2(b)Neutral of a multiphase circuit
- AS/NZS 3008.1.2:2017 Cl 3.5.9Third harmonic current in the neutral
- AS/NZS 3000:2018 Cl 3.5.2Neutral conductor of a circuit
- AS/NZS 3008.1.2:2017 Table 2Reduction factors for harmonic currents in 4- and 5‑core cables
- AS/NZS 3008.1.1:2017 Table 2Reduction factors for harmonic currents in 4- and 5‑core cables
Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi
Ngā tūtohi i arotakehia whakamutunga i te 2 Oct 2026.
Ngā taputapu hononga
- Tātaitai rahi tauraFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Tātaitai TransformerCalculate transformer full load current and impedance.Kāore he paerewa
- Iahiko neutral o tētahi uta kore tauriteThe neutral current of an unbalanced three‑phase load.AS/NZS 3000