Kōwhiri taura comms
Kōwhiria tētahi taura comms, ā, tirohia te roa o te ara.
Reads AS/NZS 3000:2018 and Industrial communications sources 2019-2024. Tables checked 26 Sept 2026.
Whakamātau mahi 8
Ka whakakī ia mahi i ngā uara tauira. Whakakapia ērā ki ō uara.
- Add an instrument loopA cable for the signal over a 150 m route.
- Select a comms cableA PROFINET cable for a 60 m run through a drag chain.
- Check an RS-485 runWhether 400 m at 115.2 kbps is in the limit.
- Check a long Modbus trunkWhether 1200 m at 9.6 kbps is in the limit.
- Check an Ethernet run past 90 mWhether a 110 m Ethernet run is in the limit.
- Pick a 24 V field supply cableA cable for a 24 V d.c. supply over 80 m.
- Pick a screened cable beside a driveA screened signal cable for a noisy area.
- Pick an outdoor Ethernet cableAn Ethernet cable for an outdoor run.
Ngā whakauru
He tauira mahi me ngā whakauru taunoa.
- Interface
- RS-485
- Taiao
- Whakaurunga mau
- Roa rerenga
- 100 m
- Rauemi kākahu
- PVC
- Kua atārangitia te taura
- Āe
- Tere tuku
- 187.5 kbps
- Whānau waea pahi
- Paerewa, pakari, FRNC, kai, whenua raro, moana rānei
Roa rerenga
Kei roto i te rohe
- Rohe roa
- 1,000m
- Hanganga waea
- 1 pair or more, 2 cores, larger than 0.34 mm2, required screen
- Atārangi
- Hiahiatia
- Tirohanga arotaki
- Angitu
- Whakamutunga i ia pito
- 120Ω
- Utaina kotahi ia raina
- 32
- Tirohanga taiao
- Angitu
- Tirohanga kāwai
- Kāore e whai pānga
- Tuhipoka
- A PROFIBUS DP segment at 187.5 kbps on standard bus cable may run 1000 m, from a cable maker network manual. The held table falls from 1000 m at 9.6 kbps to 100 m from 3 Mbps up. TIA-485 itself sets no maximum line length, and a separate report gives a nominal 1.2 km on 24 AWG cable.
He āwhina hoahoa tēnei hua. Manatokohia ki te paerewa o nāianei.
Ngā hīkoi tātaitanga
- AtangaRS-485
Industrial communications sources 2019-2024
- Roa o te rere100m
- Rohe roa1,000m
Industrial communications sources 2019-2024
- Tirohanga roaKua paahi
- Hanganga1 pair or more, 2 cores, larger than 0.34 mm2, required screen
Industrial communications sources 2019-2024
- Arotaki e hiahiatia anarequired
Industrial communications sources 2019-2024
- Tirotiro atārangiKua paahi
- TaiaoWhakauru kua whakatūria
Industrial communications sources 2019-2024
- Tirotiro taiaoKua paahi
- Tirohanga kāwaiKāore e pā
- Tere tuku187.5 kbps
- Rārangi tere kua tuhia187.5 kbps
Industrial communications sources 2019-2024
- Whānau waea pahitaura pahi paerewa
Industrial communications sources 2019-2024
- Whakamutunga i ia pito120Ω
Industrial communications sources 2019-2024
- Kawenga kotahi ia rārangi32
Industrial communications sources 2019-2024
- Ngā whakapiri pahi ia wāhanga32
Industrial communications sources 2019-2024
Mō tēnei tātaitai
How this is calculated
The tool picks the cable construction for a control or data link. It checks your run length against the limit for the interface. No AmpSize figure here comes from a printed Standard. The figures come from maker data and course notes, which the tool labels as secondary sources.
- Interface. You pick 24 V d.c., 4–20 mA, RS-485, Ethernet or PROFINET. For RS-485 you also pick the data rate and the bus cable family.
- Length limit. The tool reads the longest run for that interface. For RS-485 the limit falls as the data rate rises.
- Length check. It compares your run with the limit. It reports the run as inside or over the limit.
- Construction. It gives the pairs, the cores and the smallest core size. It says whether a screen is required, and checks the screen you enter.
- Environment. It checks the sheath and the bend radius for a fixed or a flexing installation. For Ethernet it checks the category.
- Termination. For RS-485 it gives the termination at each end and the unit loads per line.
| Step | Source | What it decides |
|---|---|---|
| Length limit | Industrial communications sources 2019 to 2024 | The longest run for the interface |
| Construction and screen | Industrial communications sources 2019 to 2024 | The cable build |
| Termination | Industrial communications sources 2019 to 2024 | The resistor at each end |
Worked example
- RS-485 at 187.5 kbps over 1200 m. The limit is 1,000 m, so the run is over the limit. The screen and environment checks pass. Add a repeater or shorten the run.
Limits
- The figures are secondary source and maker data. They are not a Standard. Confirm each one with the device maker.
- The tool does not size power conductors. Use the DC cable size calculator for a 24 V supply.
- The tool does not check segregation from power cables. Use the segregation checker.
- The termination value suits typical cable. Match it to the cable you use.
- The 32 unit loads on an RS-485 line are not a device count.
See also: Control panels and PLC wiring, 24 V DC instrument loop voltage drop and Loop power.
Pātai
He āwhina hoahoa te hua. Manatokohia ki te paerewa o nāianei.
He aha te mahi a te kōwhiri taura comms?
Ka whakaingoa i te hanganga taura mō tētahi hono 24 V DC, 4–20 mA, RS-485, Ethernet, PROFINET rānei, ā, ka kī mēnā kei roto te roa o te ara i te tepe mō taua interface. Ka arotake anō i te sheath, te screen me te ahoroa piko ki te taiao.
Kia pēhea te roa o tētahi wāhanga RS-485?
Ka whakaatu te taputapu i ngā roa segment PROFIBUS DP mai i te pukapuka a te kaihanga taura: 1000 m tae atu ki te 187.5 kbps ki te taura bus paerewa, 400 m i te 500 kbps, 200 m i te 1.5 Mbps, me te 100 m mai i te 3 Mbps ake. He poto iho ngā rerenga taura flexible me te torsion.
He aha te mea e tatauria ana e te rohe RS-485 o te 32?
Ko ngā unit load, ehara i ngā taputapu. Ka tango tētahi unit load i te 1 mA i raro i te pēhanga common-mode o te 12 V. Ka whakaatu tētahi receiver e nui ana te aukati input i runga i te 12 kilohm i tētahi wāhanga anake o tētahi, nā reira ka taea e tētahi raina te kawe neke atu i te 32 receivers.
He aha te termination e hiahiatia ana e te RS-485?
Ko te aukati whakamutunga e rite ana ki te impedance tūturu o te raina. Ko te puna tū e mahi ana ki te 120 ohm i ia pito, nō reira rite ki te taura e whakamahia ana e koe. Ko te raina e poto ana kia whakaarohia he lumped-parameter kāore e hiahia he termination.
He tepe roa pēhea e pā ana ki te 24 V DC me te 4–20 mA?
Kāore tētahi o ēnei e mau i tētahi roa kua whakapuakihia. Ka whakaaetia te rere 24 V DC e te heke volt, nā reira whakamahia te taputapu heke voltage a AmpSize i te 24 V. Ka whakaaetia te loop 4–20 mA e te loop burden me te voltage puna transmitter.
Kōrero o muri
Ngā Clause me ngā Table e pānuitia ana e tēnei taputapu
- AS/NZS 3000:2018 Table 3.3Nominal minimum cross-sectional area of conductors
- Industrial communications sources, interface limitsLength, screen and construction limits for five industrial interfaces
Ia Clause me Table, me te pēhea i manatokotia ai ia tētahi
Ngā tūtohi i arotakehia whakamutunga i te 26 Sept 2026.
Ngā taputapu hononga
- Loop power budget mō ngā loop 4-20 mACheck the voltage a 4–20 mA loop leaves the transmitter.AS/NZS 3008.1.2AS/NZS 3008.1.1
- Tātaitai heke voltageCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Kōwhiri whakawhenua screen tauraFind where to earth a screen, drain wire or armour.AS/NZS 3000
He whai hua tēnei?
He pātai, he uara rānei e kitea ana he hē? Whakapā mai.