Chọn cáp truyền thông
Chọn cáp truyền thông và kiểm tra chiều dài tuyến cáp.
Reads AS/NZS 3000:2018 and Industrial communications sources 2019-2024. Tables checked 26 Sept 2026.
Thử một công việc 8
Mỗi công việc điền sẵn giá trị ví dụ. Hãy thay bằng giá trị của bạn.
- Add an instrument loopA cable for the signal over a 150 m route.
- Select a comms cableA PROFINET cable for a 60 m run through a drag chain.
- Check an RS-485 runWhether 400 m at 115.2 kbps is in the limit.
- Check a long Modbus trunkWhether 1200 m at 9.6 kbps is in the limit.
- Check an Ethernet run past 90 mWhether a 110 m Ethernet run is in the limit.
- Pick a 24 V field supply cableA cable for a 24 V d.c. supply over 80 m.
- Pick a screened cable beside a driveA screened signal cable for a noisy area.
- Pick an outdoor Ethernet cableAn Ethernet cable for an outdoor run.
Dữ liệu nhập
Ví dụ tính toán với dữ liệu nhập mặc định.
- Giao diện
- RS-485
- Môi trường
- Lắp đặt cố định
- Chiều dài đoạn dây
- 100 m
- Vật liệu vỏ bọc
- PVC
- Cáp có màn chắn
- Có
- Tốc độ truyền
- 187.5 kbps
- Họ cáp bus
- Tiêu chuẩn, gia cường, FRNC, thực phẩm, chôn ngầm hoặc hàng hải
Chiều dài đoạn dây
Trong giới hạn
- Giới hạn chiều dài
- 1,000m
- Cấu tạo cáp
- 1 pair or more, 2 cores, larger than 0.34 mm2, required screen
- Màn chắn
- Bắt buộc
- Kiểm tra màn chắn
- Đạt
- Đầu nối ở mỗi đầu
- 120Ω
- Tải đơn vị mỗi đường dây
- 32
- Kiểm tra môi trường
- Đạt
- Kiểm tra loại
- Không áp dụng
- Ghi chú
- A PROFIBUS DP segment at 187.5 kbps on standard bus cable may run 1000 m, from a cable maker network manual. The held table falls from 1000 m at 9.6 kbps to 100 m from 3 Mbps up. TIA-485 itself sets no maximum line length, and a separate report gives a nominal 1.2 km on 24 AWG cable.
Kết quả này là công cụ hỗ trợ thiết kế. Hãy kiểm tra theo tiêu chuẩn hiện hành.
Các bước tính toán
- Giao diệnRS-485
Industrial communications sources 2019-2024
- Chiều dài đoạn cáp100m
- Giới hạn chiều dài1,000m
Industrial communications sources 2019-2024
- Kiểm tra chiều dàiĐạt
- Cấu tạo1 pair or more, 2 cores, larger than 0.34 mm2, required screen
Industrial communications sources 2019-2024
- Yêu cầu màn chắnrequired
Industrial communications sources 2019-2024
- Kiểm tra màn chắnĐạt
- Môi trườngLắp đặt cố định
Industrial communications sources 2019-2024
- Kiểm tra môi trườngĐạt
- Kiểm tra loạiKhông áp dụng
- Tốc độ truyền187.5 kbps
- Hàng tốc độ in187.5 kbps
Industrial communications sources 2019-2024
- Họ cáp buscáp bus tiêu chuẩn
Industrial communications sources 2019-2024
- Đầu cuối ở mỗi đầu120Ω
Industrial communications sources 2019-2024
- Tải đơn vị trên mỗi đường dây32
Industrial communications sources 2019-2024
- Số thiết bị kết nối trên mỗi đoạn bus32
Industrial communications sources 2019-2024
Giới thiệu công cụ tính này
How this is calculated
The tool picks the cable construction for a control or data link. It checks your run length against the limit for the interface. No AmpSize figure here comes from a printed Standard. The figures come from maker data and course notes, which the tool labels as secondary sources.
- Interface. You pick 24 V d.c., 4–20 mA, RS-485, Ethernet or PROFINET. For RS-485 you also pick the data rate and the bus cable family.
- Length limit. The tool reads the longest run for that interface. For RS-485 the limit falls as the data rate rises.
- Length check. It compares your run with the limit. It reports the run as inside or over the limit.
- Construction. It gives the pairs, the cores and the smallest core size. It says whether a screen is required, and checks the screen you enter.
- Environment. It checks the sheath and the bend radius for a fixed or a flexing installation. For Ethernet it checks the category.
- Termination. For RS-485 it gives the termination at each end and the unit loads per line.
| Step | Source | What it decides |
|---|---|---|
| Length limit | Industrial communications sources 2019 to 2024 | The longest run for the interface |
| Construction and screen | Industrial communications sources 2019 to 2024 | The cable build |
| Termination | Industrial communications sources 2019 to 2024 | The resistor at each end |
Worked example
- RS-485 at 187.5 kbps over 1200 m. The limit is 1,000 m, so the run is over the limit. The screen and environment checks pass. Add a repeater or shorten the run.
Limits
- The figures are secondary source and maker data. They are not a Standard. Confirm each one with the device maker.
- The tool does not size power conductors. Use the DC cable size calculator for a 24 V supply.
- The tool does not check segregation from power cables. Use the segregation checker.
- The termination value suits typical cable. Match it to the cable you use.
- The 32 unit loads on an RS-485 line are not a device count.
See also: Control panels and PLC wiring, 24 V DC instrument loop voltage drop and Loop power.
Câu hỏi
Kết quả chỉ là công cụ hỗ trợ thiết kế. Đối chiếu với tiêu chuẩn hiện hành.
Công cụ Chọn cáp truyền thông làm gì?
Công cụ nêu cấu tạo cáp cho liên kết 24 V DC, 4–20 mA, RS-485, Ethernet hoặc PROFINET, và cho biết chiều dài tuyến có nằm trong giới hạn của giao tiếp đó hay không. Công cụ cũng kiểm tra vỏ bọc, lớp chống nhiễu và bán kính uốn so với môi trường.
Một đoạn RS-485 có thể dài bao nhiêu?
Công cụ báo chiều dài đoạn PROFIBUS DP theo sổ tay của nhà sản xuất cáp: 1000 m tới 187.5 kbps với cáp bus tiêu chuẩn, 400 m ở 500 kbps, 200 m ở 1.5 Mbps và 100 m từ 3 Mbps trở lên. Tuyến cáp mềm và cáp xoắn ngắn hơn.
Giới hạn 32 của RS-485 đếm những gì?
Tính theo tải đơn vị, không phải thiết bị. Một tải đơn vị lấy 1 mA dưới ứng suất chế độ chung 12 V. Bộ thu có điện trở đầu vào trên 12 kilohm chỉ chiếm một phần của một tải đơn vị, nên một đường dây có thể mang hơn 32 bộ thu.
RS-485 cần loại đầu cuối nào?
Điện trở đầu cuối bằng trở kháng đặc trưng của đường dây. Nguồn giữ hoạt động tới 120 ohm ở mỗi đầu, nên hãy khớp với cáp bạn dùng. Đường dây đủ ngắn để coi là tham số tập trung thì không cần đầu cuối.
Giới hạn chiều dài nào áp dụng cho 24 V DC và 4–20 mA?
Cả hai đều không có chiều dài công bố. Tuyến 24 V DC bị giới hạn bởi sụt áp, nên hãy dùng công cụ sụt áp của AmpSize ở 24 V. Mạch vòng 4–20 mA bị giới hạn bởi tải của mạch vòng và điện áp cấp cho bộ truyền tín hiệu (transmitter).
Nền
Các điều khoản và bảng mà công cụ này đọc
- AS/NZS 3000:2018 Table 3.3Nominal minimum cross-sectional area of conductors
- Industrial communications sources, interface limitsLength, screen and construction limits for five industrial interfaces
Mọi điều khoản và bảng, kèm cách mỗi mục đã được kiểm chứng
Các bảng được kiểm tra lần cuối ngày 26 Sept 2026.
Công cụ liên quan
- Quỹ công suất cho mạch vòng 4-20 mACheck the voltage a 4–20 mA loop leaves the transmitter.AS/NZS 3008.1.2AS/NZS 3008.1.1
- Công cụ tính sụt ápCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Công cụ chọn nối đất lớp chống nhiễu cápFind where to earth a screen, drain wire or armour.AS/NZS 3000