AS/NZS 3008.1.1:2017
Table 23
Grouping factors for single‑core circuits on trays, ladder supports, racks and cleats in air
With the AU standard, the cable size and correction factors tools read this table for single‑core circuits on a tray, a ladder, a rack or cleats. The values print the same as the New Zealand part.
Kua manatokotia: pānuitia ki te paerewa tā, whārangi 80. I tirohia 26 Sept 2026.
Ngā unit: Tiers count, Count circuits per tier or row
Ko ēnei ngā uara e tuhia ana e AmpSize. Kāore he kupu o te paerewa e tuhia ana. Whakamanahia ki te paerewa o nāianei.
22 rārangi
| Item | Installation | Spacing | Tiers (count) | Factors |
|---|---|---|---|---|
| 1 | unperforated-trays | touching | 1 | 0.95, 0.85, 0.84 |
| 2 | unperforated-trays | touching | 2 | 0.92, 0.83, 0.79 |
| 3 | unperforated-trays | touching | 3 | 0.91, 0.82, 0.76 |
| 4 | perforated-trays | touching | 1 | 0.97, 0.89, 0.87 |
| 5 | perforated-trays | touching | 2 | 0.94, 0.85, 0.81 |
| 6 | perforated-trays | touching | 3 | 0.93, 0.84, 0.79 |
| 7 | ladder-supports-racks-cleats | touching | 1 | 1, 0.95, 0.94 |
| 8 | ladder-supports-racks-cleats | touching | 2 | 0.95, 0.9, 0.88 |
| 9 | ladder-supports-racks-cleats | touching | 3 | 0.95, 0.89, 0.85 |
| 10 | vertical-perforated-trays | touching | 1 | 0.94, 0.85, — |
| 11 | vertical-perforated-trays | touching | 2 | 0.92, 0.83, — |
| 12 | unperforated-trays | spaced | 1 | 0.95, 0.95, 0.94 |
| 13 | unperforated-trays | spaced | 2 | 0.92, 0.91, 0.87 |
| 14 | unperforated-trays | spaced | 3 | 0.91, 0.9, 0.85 |
| 15 | perforated-trays | spaced | 1 | 0.97, 0.97, 0.96 |
| 16 | perforated-trays | spaced | 2 | 0.94, 0.93, 0.89 |
| 17 | perforated-trays | spaced | 3 | 0.93, 0.92, 0.86 |
| 18 | ladder-supports | spaced | 1 | 1, 1, 1 |
| 19 | ladder-supports | spaced | 2 | 0.95, 0.95, 0.93 |
| 20 | ladder-supports | spaced | 3 | 0.95, 0.94, 0.9 |
| 21 | vertical-perforated-trays | spaced | 1 | 1, 0.91, 0.89 |
| 22 | vertical-perforated-trays | spaced | 2 | 1, 0.9, 0.86 |