Table 23

Grouping factors for single‑core circuits on trays, ladder supports, racks and cleats in air

With the AU standard, the cable size and correction factors tools read this table for single‑core circuits on a tray, a ladder, a rack or cleats. The values print the same as the New Zealand part.

Na-verify: binasa laban sa naka-print na standard, mga pahina 80. Na-check noong 26 Sept 2026.

Mga unit: Tiers count, Count circuits per tier or row

Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.

Bumalik sa card nito sa page ng AS/NZS 3008.1.1:2017

22 na row

Table 23, Grouping factors for single-core circuits on trays, ladder supports, racks and cleats in air
ItemInstallationSpacingTiers (count)Factors
1unperforated-traystouching10.95, 0.85, 0.84
2unperforated-traystouching20.92, 0.83, 0.79
3unperforated-traystouching30.91, 0.82, 0.76
4perforated-traystouching10.97, 0.89, 0.87
5perforated-traystouching20.94, 0.85, 0.81
6perforated-traystouching30.93, 0.84, 0.79
7ladder-supports-racks-cleatstouching11, 0.95, 0.94
8ladder-supports-racks-cleatstouching20.95, 0.9, 0.88
9ladder-supports-racks-cleatstouching30.95, 0.89, 0.85
10vertical-perforated-traystouching10.94, 0.85, —
11vertical-perforated-traystouching20.92, 0.83, —
12unperforated-traysspaced10.95, 0.95, 0.94
13unperforated-traysspaced20.92, 0.91, 0.87
14unperforated-traysspaced30.91, 0.9, 0.85
15perforated-traysspaced10.97, 0.97, 0.96
16perforated-traysspaced20.94, 0.93, 0.89
17perforated-traysspaced30.93, 0.92, 0.86
18ladder-supportsspaced11, 1, 1
19ladder-supportsspaced20.95, 0.95, 0.93
20ladder-supportsspaced30.95, 0.94, 0.9
21vertical-perforated-traysspaced11, 0.91, 0.89
22vertical-perforated-traysspaced21, 0.9, 0.86