Paghahambing ng motor starting method
Ikumpara ang DOL, star-delta, soft start at drive starts.
Subukan ang isang job 4
Nilalagyan ng halimbawang value ang bawat job. Palitan ang mga ito ng sarili mong value.
- Compare starters for a centrifugal pumpStart current and torque of six methods for a 15 kW pump.
- Check star-delta on a loaded conveyorWhich starts a 22 kW conveyor that needs high breakaway torque.
- Estimate the dip of a fan startThe voltage dip of each method for a 37 kW fan.
- Start a bore pump on a weak supplyThe dip of a 5.5 kW pump at the end of a rural line.
Mga input
Worked example gamit ang mga default na input.
- Shaft power
- 11 kW
- Line voltage
- 400 V
- Power factor
- 0.85
- Efficiency
- 0.9
- Locked-rotor current
- 6 x
- Locked-rotor torque
- 200 %
- Load breakaway torque
- 30 %
- Tap ng autotransformer
- 65 %
- Primary resistance, boltahe sa motor
- 70 %
- Current limit ng soft starter
- 3.5 x
- Current limit ng drive
- 150 %
- Fault level sa motor
- 0 kA
Pinakamababang start current na nagpapaandar sa load
Variable speed drive
- Full load current
- 20.75A
- Starting current, DOL
- 124.5A
- Starting current, napiling paraan
- 31.13A
- Starting torque, napiling paraan
- 150%
Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.
Mga hakbang ng kalkulasyon
- Full load current20.75A
Induction motor at standstill: current with the voltage, torque with its square.
- Full load torque72.2Nm
- Locked-rotor current124.5A
- Locked-rotor torque200%
- Load breakaway torque30%
- Starting current, Direct on line124.5A
- Starting torque, Direct on line200%
- Starting current, Star-delta41.5A
- Starting torque, Star-delta66.7%
- Starting current, Autotransformer52.6A
- Starting torque, Autotransformer84.5%
- Starting current, Primary resistance87.15A
- Starting torque, Primary resistance98%
- Starting current, Soft starter72.63A
- Starting torque, Soft starter68.1%
- Starting current, Variable speed drive31.13A
- Starting torque, Variable speed drive150%
Tungkol sa calculator na ito
How this is calculated
You give the motor's shaft power, line voltage, power factor and efficiency. The tool works the full load current and full load torque the same way the motor tool does. Then you give the locked-rotor current and torque from the motor data, and the torque the load needs to break away from rest.
A cage induction motor at standstill behaves like a transformer with its secondary shorted. Its current follows the voltage at its terminals, and its torque follows the square of that voltage. Every starting method is a way of lowering the voltage at the motor, or of controlling the current directly. So the tool scales the locked-rotor current and torque for each method:
- direct on line takes the full locked-rotor current and torque;
- star-delta puts the line voltage divided by the square root of 3 across each winding, so the line current and the torque both fall to a third;
- an autotransformer at a tap gives the motor the tap voltage; the motor current falls with the tap, the line current and the torque with the tap squared;
- primary resistance leaves part of the voltage at the motor; the current falls with it, the torque with its square;
- a soft starter holds the current at its limit, and the torque falls with the square of that limit over the locked-rotor current;
- a drive starts at rated flux, so its torque follows its current limit.
A method starts the load where its starting torque is above the breakaway torque. With a fault level at the motor terminals, the tool estimates the dip as the starting current over the fault current.
| Step | Table or clause | What it decides |
|---|---|---|
| Full load current and torque | The motor tool's method | The base for every multiple |
| Direct on line | Locked-rotor data | The highest current and torque |
| Star-delta | One third of each | The current and torque in star |
| Autotransformer and primary resistance | Voltage ratio and its square | The current and torque at the tap |
| Soft starter and drive | Current limit | The current and torque each allows |
| Starts the load | Breakaway torque | Which methods start it |
Worked examples
- An 11 kW centrifugal pump. Every method starts it. Direct on line draws 124.5 A and star-delta 41.5 A. The lowest start that still turns the pump is the variable speed drive, at 31.13 A.
- A 22 kW loaded conveyor. Star-delta gives 73.3 % torque against a 120 % load, so it cannot start the belt. The lowest start that does is direct on line, at 290.57 A.
- A 37 kW fan on a board with 6 kA. The dip is 8.1 % direct on line and 2.7 % in star-delta. The lowest start is the variable speed drive, at 104.72 A and a 1.7 % dip.
- A 5.5 kW bore pump at the end of a rural line. Direct on line dips the supply 9.1 %, a soft starter at 3.5 times full load current 4.5 %. The lowest start is the variable speed drive, at 15.57 A.
Limits
The comparison is at standstill. It does not follow the torque through the run-up, so a star-delta start that breaks the load away can still stall before the change to delta. The drive figures assume rated flux; the supply side of a drive draws less than the motor side at low speed. The dip is an estimate for comparing methods, not a flicker study. Choose the circuit-breaker so its magnetic trip clears the starting current of the method used, and set the overload to the full load current.
See also: Motor starting methods: current and torque, Starting a loaded conveyor and Motor.
Mga tanong
Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.
Gaano kababa ang nababawas ng star-delta sa starting current?
Sa isang katlo ng direct on line current, dahil bawat winding ay nakakakita ng line voltage na hinati sa square root ng 3 sa simula. Bumababa rin sa isang katlo ang starting torque.
Masisimulan ba ng star-delta ang load ko?
Sa mga kaso lang na ang isang katlo ng locked-rotor torque ay nasa itaas ng load breakaway torque. Karaniwang nagsisimula ang fan o centrifugal pump; ang loaded conveyor o crusher ay madalas hindi. Minamarkahan ng tool ang bawat method na nagpapasimula ng load.
Ano ang ginagawa ng autotransformer tap?
Sa 65 % tap, 65 % ng voltage ang nakikita ng motor. Bumababa ang motor current at torque kasabay ng tap, at bumababa ang line current sa tap na naka-square, kaya ang 65 % tap ay humihila ng humigit-kumulang 42 % ng direct on line current.
Bakit pinakamababa ang current na kinukuha ng drive sa simula?
Sinisimulan ng drive ang motor sa mababang frequency na may rated flux, kaya nagbibigay ito ng full load torque sa halos full load current. Kinukuha ng tool ang drive current limit bilang starting current at torque.
Paano kinakalkula ang voltage dip?
Ito ay ang starting current na hinati sa prospective fault current sa motor terminals. Ito ay estimate na kumukuha ng source at start sa parehong power factor. Gamitin ito para ikumpara ang mga paraan, hindi bilang flicker study.
Mga worked example
Background
Mga kaugnay na tool
- Generator sizing mula sa load listSize a generator from a load list with motor starting.Walang standard
- Motor calculatorFind motor full load current, starting current and torque.Walang standard
- Motor circuit calculatorCable, breaker, contactor and overload for one motor.AS/NZS 3000AS/NZS 3008.1.2AS/NZS 3008.1.1