Motor starting methods: current and torque

Working level

A drawn boards and supply schematic for Motor starting methods: supply, meter, main switchboard, lighting, socket-outlets and motor.

A three‑phase cage motor at standstill is like a transformer with a shorted secondary. The rotor is not turning, so nothing opposes the supply but the windings' impedance. The motor draws its locked-rotor current: often six to eight times its full load current. A starter exists to bring that current down. Every way of doing it has a cost in torque.

The two rules

At standstill:

  1. The current follows the voltage at the motor terminals. Half the voltage, half the current.
  2. The torque follows the square of that voltage. Half the voltage, a quarter of the torque.

So a starter that cuts the voltage cuts the torque faster than the current.

The methods

MethodLine currentStarting torque
Direct on lineThe locked-rotor currentThe locked-rotor torque
Star-deltaOne thirdOne third
Autotransformer at tap kk squared of itk squared of it
Primary resistance leaving kk of itk squared of it
Soft starter, current limitThe limitThe limit over the locked-rotor current, squared
Variable speed driveAbout its current limitAbout its current limit, as a share of full load torque
  • Star-delta. In star each winding sees the line voltage over the square root of 3. Its current falls by that factor, and the line current falls by it again, because the windings are in star. The result is a third of the current and a third of the torque.
  • Autotransformer. The motor sees the tap voltage, so its current and torque fall as before. The transformer then steps the current down again on the line side. The line current and the torque both fall with the tap squared: a 65 % tap gives about 42 % of each.
  • Soft starter. It holds the current at a limit by lowering the voltage. The torque is still the voltage squared, so a soft starter at 3.5 times full load current on a motor of 6 times gives about a third of the locked-rotor torque.
  • Variable speed drive. It starts the motor at low frequency with the voltage scaled to keep the flux. The motor runs on the steep part of its curve, so it gives full load torque at about full load current. It is the only method that cuts the current without cutting the torque.

Will it start the load?

A method starts the load where its starting torque is above the torque the load needs to break away. A fan or centrifugal pump needs little at standstill, so every method starts it. A loaded conveyor, a crusher or a positive displacement pump may need full load torque or more. Star-delta's third is then not enough.

The dip

The starting current flows through the supply's impedance and pulls the voltage down. A rough estimate is the starting current over the fault current at the motor: 290 A from a 4 kA supply is about a 7 % dip.

Compare the methods for a motor with the motor starting tool. A worked conveyor is in Starting a loaded conveyor.