NZS 4512:2010
Cl 211, 212, 213, 602.7
Fire alarm standby battery periods, cell voltages and test criterion
The fire alarm battery tool reads the two standby periods, the alarm period, the recharge period, the float voltage and its tolerance, the current limit voltage, the nominal cell voltage, the service life and the three monthly test figures, from Clauses 211.5, 212, 213 and 602.7. The periods are minimum periods, so the tool holds a minimum capacity before the factors and never reports less than that figure.
Na-verify: binasa laban sa naka-print na standard, mga pahina 28–30, 73. Na-check noong 26 Sept 2026.
Mga unit: Value h, min, V per cell, years, s or percent
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
12 na row
| Value (h, min, V per cell, years, s or percent) |
|---|
| 24 |
| 72 |
| 30 |
| 24 |
| 2.2 |
| 0.03 |
| 1.85 |
| 2 |
| 5 |
| 10 |
| 5 |
| 80 |