The energy demand method and Table C3

المستوى العملي

A drawn floor plan with shop, office and carpark areas, each labelled with a VA per square metre figure.

The energy demand method gives the maximum demand of a building from its floor area. You do not list each load. You multiply each area by a figure in VA per square metre. AS/NZS 3000:2018 sets the method in App C Para C2.4.3, with the figures in Table C3. The floor area demand calculator does the sums.

Why use floor area

Early in a design, you do not know every light, socket and air conditioner. You know the floor area and the use. A shop, an office and a warehouse draw very different loads for each square metre. Table C3 gives a figure for each use. That makes it a quick method for a tender, a supply application or a first board size.

The method is for commercial and light-industrial buildings. For a home, use Table C1. See Maximum demand and diversity.

What the figure means

Each figure is a demand in VA for each square metre of floor. It already allows for loads that do not all run at full power at once. You do not apply a second diversity factor on top.

Table C3 prints a range and an average for most uses. Offices with light and power run from 40 to 60 VA/m², with an average of 50. Retail light and power runs from 40 to 100, with an average of 70.

Range or average

The average suits most designs. Move to the high end for a hot climate, long hours or a heavy fit-out. Move to the low end only when you know the load is light and managed. You can also enter your own figure, for example from a measured building of the same kind.

The range moves the answer a long way. In the guide for a small retail and office building, the low end gives 66 kVA and the high end gives 135 kVA. The average gives 100.5 kVA. Show the range to the client, not one number only.

What drives the figure

  • The use. Shops need much more lighting and power than warehouses.
  • Air conditioning. The type matters. Variable volume prints one figure, 20 VA/m². Zonal reheat runs from 40 to 60.
  • The climate. A hot site runs its cooling harder and for longer.
  • The hours. A building that runs all day has less diversity than one that runs in the day only.
  • Energy management. A system that limits the load can lower the figure.

EV charging goes on top

The NOTE to Table C3 says EV charging is in addition to all other energy demands. Carparks have separate EV rows, one for open air and one for a basement. Keep the plain carpark row for lighting and ventilation. Add the EV row for the charging. The tool adds the EV kVA to the total. For the charger side, see EV charging load and spare capacity.

Special equipment

Table C3 prints no figure for special equipment in warehouses and light industry. It points you to the load details. So you take the kVA from the plate or the maker's data, and enter it. The tool adds it as it is.

A 2000 m² warehouse with light, ventilation and 30 kVA of special equipment gives 60 kVA. That is 86.96 A per phase at 230 V.

From kVA to amps

The total is in kVA. The supply current depends on the phases.

  • On one phase, current = kVA × 1000 ÷ phase voltage.
  • On three phases, current in each phase = kVA × 1000 ÷ (3 × phase voltage).

The three‑phase sum assumes the load spreads evenly over the phases. Where it does not, find the heaviest phase. See Maximum demand per phase on a three‑phase supply.

The Paragraph C2.4.3.2 case shows the sum. 1500 m² of office at 50 VA/m² for light and power and 50 VA/m² for zonal reheat gives 150 kVA. At 230 V, that is 217.39 A per phase.

When to move to Table C2

Use Table C2 when you know the loads. It sorts each load into a group and applies a demand to each group. It suits a fit-out, a kitchen or a plant room, where the equipment is known. Use Table C3 when you have only areas.

The Maximum Demand tool runs Table C2. The Table C2 tender guide shows it on a real case. Run both methods and compare. If they differ widely, find out why before you size the supply.