电缆桥架与梯架填充率
桥架或梯架宽度、层数、kg/m 及成组系数。
Reads AS/NZS 3000:2018, Nexans Olex The Handbook:2017, AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3008.1.1:2017 (AU). Tables checked 1 Oct 2026.
尝试一个工程 4
每项工作都会预填示例数值。请替换为您自己的数值。
- Fill a plant room trayTen multicore cables on a perforated tray, with the factor for cable size.
- Lay trefoil submains on a ladderTwo single‑core circuits in trefoil, their width and kg/m.
- Find the tiers for ten feedersHow many tiers ten multicore feeders need on a narrow tray.
- Space flat mains on a ladderThree flat circuits spaced on an Australian ladder, with the grouping factor.
输入
使用默认输入值的示例计算。
- 标准
- AS/NZS 3008.1.2(新西兰)
- 支撑
- 有孔线槽
- 内宽
- 300 mm
- 保持净空的宽度
- 25 %
- 电缆
- 多芯(三芯加地)
- 间距
- 接触敷设
- 桥架上的电缆
- 2 行
所需层数
1
- 电缆占用的宽度
- 125.3mm
- 最满一层的填充率
- 41.8%
- 最重一层的电缆质量
- 4.31kg/m
- 用于确定电缆规格的成组系数
- 0.73
此结果仅供设计参考。请对照现行标准进行核验。
计算步骤
- 4 × 16 mm² 多芯,每根 19.7 mm78.8mm
- 3 × 6 mm² 多芯,每根 15.5 mm46.5mm
- 电缆占用的宽度125.3mm
- 扣除 25 % 余量后的可用宽度225mm
- 所需层数结果1
AS/NZS 3008.1.2:2017 Table 24 Note 5
- 第 1 级:7 根电缆,125.3 mm4.31kg/m
Olex Handbook
- 最满一层的填充率41.8%
- 用于确定电缆规格的成组系数×0.73
AS/NZS 3008.1.2:2017 Table 24 p.82
关于此计算器
How this is calculated
A cable tray or ladder holds cables side by side. AS/NZS 3008.1 rates cables on trays and ladders with grouping factors that hold for one layer of cables on each tier. So the question for a tray is how wide the cables are, laid in one layer, and how many tiers that takes. This tool lays them out and reads the factor.
You pick the cable family and list the sizes and counts. The overall diameters are the cable maker's figures that the conduit fill tool also uses. A multicore cable takes one diameter of width. A single‑core three‑phase circuit takes two diameters in trefoil and three laid flat. Touching cables sit side by side. Spaced cables have one diameter between them, as Tables 23 and 24 draw, and where sizes differ the tool uses the largest.
The standard sets no fill percentage for a tray, so the width kept free for later cables is yours to choose. The tool places each cable or circuit, in the order you list them, on the first tier with room. A run that does not fit one tier takes another, and stacked tiers are at least 300 mm apart for the factors to hold.
It then reads the grouping factor for the support, the spacing, the tiers used and the most cables or circuits on one tier. A count between two printed columns reads the next column up. Past the printed counts no factor is given. The mass per metre on each tier is the maker's catalogue figure.
| Step | Table or clause | What it decides |
|---|---|---|
| Cable diameters | Olex and Prysmian catalogue diameters | The width each cable or circuit takes |
| Spacing | AS/NZS 3008.1 Tables 23 and 24 Note 1 | One diameter between spaced cables or circuits |
| One layer per tier | AS/NZS 3008.1 Tables 23 and 24 Note 5 | The tiers the run needs |
| Tier spacing | AS/NZS 3008.1 Tables 23 and 24 Note 6 | The gap between stacked tiers |
| Grouping factor | AS/NZS 3008.1 Table 23 or Table 24 | The factor to carry to the cable size |
| Mass | Olex Handbook mass per metre | The kg/m on each tier |
Worked examples
- A plant room tray: four 16 mm² and three 6 mm² multicore cables fit on 1 tier of a 300 mm perforated tray. They take 125.3 mm, a grouping factor of 0.73.
- Two 95 mm² trefoil submains on a 450 mm ladder fit on 1 tier, 60.8 mm wide, with a grouping factor of 0.95.
- Ten 35 mm² multicore feeders on a 300 mm tray need 2 tiers with a quarter of the width kept free. The fullest tier carries nine cables, a grouping factor of 0.68.
- Three flat 240 mm² circuits spaced on a 600 mm Australian ladder fit on 1 tier at a grouping factor of 1.
Limits
The tool lays one cable family at a time: multicore three core and earth cables, or single‑core three‑phase circuits. It does not mix the two, model cables in more than one layer, or check segregation between services on the same tray. Use the segregation tool for that.
Single‑core widths use the diameter of unsheathed V‑90 single cores, the conduit fill figures. A sheathed or XLPE single core is wider, so allow for it. The mass is the cable alone. Check the tray or ladder against its maker's load and span tables, with the fixings and any future cables.
See also: Cable size, Correction factors and Conduit fill.
问题
结果仅供设计参考。请依据现行标准核对。
电缆桥架是否有最大填充率?
AS/NZS 3008.1 未规定桥架或梯架的填充百分比。其成组系数假定每层仅敷设一层电缆。本工具按一层敷设,并保留您所选择的供后续电缆使用的余量。
桥架上的间隔敷设是什么意思?
按 AS/NZS 3008.1 Tables 23 和 24 所示,间隔敷设的电缆之间留有一个电缆外径的间距。截面不同时,本工具采用最大外径。间隔敷设会提高成组系数,并占用更大宽度。
三角形(品字形)排列的回路宽度是多少?
三根单芯电缆呈品字形排列时,在桥架上占两倍直径的宽度。平放时则占三倍直径。本工具采用电缆制造商产品目录中的外径。
电缆截面应采用什么成组系数?
工具按所用层数及单层最多电缆根数,读取 AS/NZS 3008.1 Table 23(单芯回路)或 Table 24(多芯电缆)。将所得系数输入电缆截面工具。
是否检查桥架能否承受重量?
否。它依据制造商目录给出每层电缆的千克每米重量。请对照桥架制造商的载荷与跨距表进行核对。
计算示例
背景
本工具读取的条款和表格
- AS/NZS 5000.1 cables, manufacturer dataCable overall diameters
- AS/NZS 3008.1.2:2017 Table 23Grouping factors for single‑core circuits on trays, ladder supports, racks and cleats in air
- AS/NZS 3008.1.2:2017 Table 24Grouping factors for multicore cables on trays, ladder supports, racks and cleats in air
- AS/NZS 3008.1.1:2017 Table 23Grouping factors for single‑core circuits on trays, ladder supports, racks and cleats in air
- AS/NZS 3008.1.1:2017 Table 24Grouping factors for multicore cables on trays, ladder supports, racks and cleats in air
- cable-massApproximate cable mass per metre
表格最后核对于 1 Oct 2026。
相关工具
这是否有用?
有问题,或数值看起来有误?联系我们。