AmpSize

配电箱分隔形式检查器

检查配电箱的分隔、通道和净距。

Reads AS/NZS 3000:2018. Tables checked 26 Sept 2026.

输入

使用默认输入值的示例计算。

每相配电盘额定值
400 A
配电盘长度
2 m
住宅安装
否
额定冲击耐受电压 Uimp
6 kV,装置电源进线端
配电盘位于需进入后方可接近的房间内
是
配电板前方留出净空
0 m

Cl 2.5.5 适用于该配电板

否

进线电源导体,Cl 2.5.5.1
不需要
内部隔离,Cl 2.5.5.2 途径
不需要
适合该路径的形式,附录 K 示例
3b or 4a or 4b
距每个需要检修的面的净空
1m
配电板周围的无阻挡空间
0.6m
应急出口通道
足以撤离,未设数量
Uimp 6 kV 时的净距,附录 K 示例
5.5mm

此结果仅供设计参考。请对照现行标准进行核验。

计算步骤

  1. Cl 2.5.5 适用于此配电板结果否

    AS/NZS 3000:2018 Cl 2.5.5

  2. 绝缘或隔离进线导体,Cl 2.5.5.1不需要

    AS/NZS 3000:2018 Cl 2.5.5

  3. 内部隔离,Cl 2.5.5.2 途径不需要

    AS/NZS 3000:2018 Cl 2.5.5

  4. 可接受的隔离形式,任选其一,App K example3b or 4a or 4b

    AS/NZS 3000:2018 App K Para K6.2

  5. 可接受的形式后缀,App K examplei, h, ih

    AS/NZS 3000:2018 App K Para K6.2

  6. 各形式的隔离对象,App K exampleTable K2

    AS/NZS 3000:2018 App K Table K2

  7. 距每个需要检修的面的净距1m

    AS/NZS 3000:2018 Cl 2.10.2.2

  8. 配电箱周围无阻碍空间0.6m

    AS/NZS 3000:2018 Cl 2.10.2.2

  9. 应急出口通道足以撤离,未设数量

    AS/NZS 3000:2018 Cl 2.10.2.2

  10. 门洞最小净宽该配电板无对应数值

    AS/NZS 3000:2018 Cl 2.10.2.2

  11. 门洞最小净高该配电板无对应数值

    AS/NZS 3000:2018 Cl 2.10.2.2

  12. Uimp 6 kV,App K example 处的过电压类别IV

    AS/NZS 3000:2018 App K Para K6.4

  13. Uimp 6 kV 处的净空,App K example5.5mm

    AS/NZS 3000:2018 App K Para K6.4

  14. Uimp 6 kV 处的替代试验电压,kV 有效值,App K example5.1

    AS/NZS 3000:2018 App K Para K6.4

  15. 爬电距离,Ui 440 V,污染等级 3,材料组 III,App K example6.3mm

    AS/NZS 3000:2018 App K Para K6.5

关于此计算器

How this is calculated

The tool checks whether Clause 2.5.5 of AS/NZS 3000:2018 asks for separation inside a switchboard. It also reads the access and exit figures of Clause 2.10.2.2 and the Appendix K examples.

  1. Scope. It compares the board rating with the Cl 2.5.5 threshold. At or above it, Cl 2.5.5 applies.
  2. Incoming conductors. Where Cl 2.5.5 applies, the incoming supply conductors are insulated or separated (Cl 2.5.5.1).
  3. Internal separation. The tool says if the Cl 2.5.5.2 route needs internal separation. It lists the forms that suit that route, from Paragraph K6.2 and Table K2.
  4. Access. From Cl 2.10.2.2 it gives the clearance from each face that needs access. It also gives the unimpeded space around the board. A domestic board has its own front clearance.
  5. Exits. A switchroom can pass the rating or length trigger. Then the tool gives the exit count and doorway size.
  6. Clearance example. It reads the Appendix K clearance for the impulse voltage you pick (Paragraphs K6.4 and K6.5).
StepTable or clauseWhat it decides
Scope and separationAS/NZS 3000 Cl 2.5.5Whether the board needs separation
FormsApp K Para K6.2 and Table K2The forms that suit
Access and exitsCl 2.10.2.2Clearances, exits and doorways
ClearancesApp K Para K6.4 and K6.5The worked examples

Worked example

A 1000 A commercial board in a switchroom. Cl 2.5.5 applies and internal separation is required. Forms 3b, 4a or 4b suit. The tool gives 2 exit paths, set well apart. The Appendix K clearance at 6 kV is 5.5 mm.

Limits

  • Appendix K is informative. Its clearance and creepage figures are examples. Verify them to AS/NZS 61439.1.
  • The tool holds the Cl 2.5.5.2 route only. Cl 2.5.5.1 offers other routes.
  • Under the trigger, the tool gives no exit count and no doorway size.
  • Measure each clearance with the doors and gear in the positions the clause names.
  • Door swing and hold-open rules appear as warnings only.

See also: Industrial switchboards, Switchboard fault rating and busbar withstand and the fault rating calculator.

问题

结果仅供设计参考。请依据现行标准核对。

配电箱何时需要内部分隔?

AS/NZS 3000:2018 Clause 2.5.5 适用于每相 800 A 及以上的配电箱。输入额定值后,AmpSize 会告知该配电箱是否满足该触发条件。Clause 2.5.5.1 还要求对每条路径上的进线导体进行绝缘或分隔。Clause 2.5.5.2 随后规定了配电箱所需的内部分隔。

接受哪些分隔形式?

Appendix K Paragraph K6.2 列出 Form 3b、Form 4a 和 Form 4b,以及带 i、h 和 ih 后缀的相同形式。Table K2 显示各形式所分隔的内容。Appendix K 为资料性附录,因此应将这些视为通向 Clause 2.5.5.2 的示例路径,而非标准所规定的数值。

配电箱周围需要多大空间?

Clause 2.10.2.2.1 规定,需要操作的每个面须留出 1.0 m。家用装置可在配电箱正面采用 0.6 m。AmpSize 对正面采用该放宽值,其他面仍保持 1.0 m。该条款规定配电箱周围应有 0.6 m 无障碍空间。请阅读该条款,了解其所假定的门和开关设备位置。

何时需要两条紧急出口路径?

Clause 2.10.2.2.2 规定,若必须进入房间才能接近配电箱,则应设两条相距较远的出口通道。每相 800 A 及以上,或长度超过 3 m 时适用。若门打开且设备抽出时,前方仍保持 3 m 通道,则一条通道即可。其他配电箱需要足够的出口通道,但不规定具体数量。

工具读取哪个版本,又遗漏了什么?

该工具依据 AS/NZS 3000:2018 并纳入修订 1、2 和 3。修订 2 重写了 Clause 2.10.2.2。修订 3 仅删除了 Clause 2.5.5 中对 AS/NZS 3439 的引用。工具收录 Clauses 2.5.5 和 2.10.2.2,以及Appendix K 的段落 K6.2、K6.4 和 K6.5。额定同时系数和温升检查属于 AS/NZS 61439 系列,因此本工具两者均未收录。

计算示例

背景

本工具读取的条款和表格

所有条款和表格,及各自的核验方式

表格最后核对于 26 Sept 2026。